Settings - ABB Relion SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

1MRS758407 B
8.1.7
Table 262:
CBXCBR Non group settings (Basic)
Parameter
Values (Range)
Operation
Select timeout
Pulse length
Table continues on next page
SMU615
Technical Manual
Name
BLK_CLOSE
AU_OPEN
AU_CLOSE
ITL_BYPASS
1) Not available for monitoring
2) Always direct operation
Table 260:
DCXSWI Output signals
Name
SELECTED
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
Table 261:
ESXSWI Output signals
Name
SELECTED
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD

Settings

Unit
1=on
5=off
10000...300000
ms
10...60000
ms
Type
Default
Description
BOOLEAN
0=False
Blocks closing
BOOLEAN
0=False
Executes the command for open direction
BOOLEAN
0=False
Executes the command for close direction
BOOLEAN
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Type
Description
BOOLEAN
Object selected
BOOLEAN
Executes the command for open direction
BOOLEAN
Executes the command for close direction
BOOLEAN
Apparatus open position
BOOLEAN
Apparatus closed position
BOOLEAN
Apparatus position is ok
BOOLEAN
Opening is enabled based on the input status
BOOLEAN
Closing is enabled based on the input status
Type
Description
BOOLEAN
Object selected
BOOLEAN
Executes the command for open direction
BOOLEAN
Executes the command for close direction
BOOLEAN
Apparatus open position
BOOLEAN
Apparatus closed position
BOOLEAN
Apparatus position is ok
BOOLEAN
Opening is enabled based on the input status
BOOLEAN
Closing is enabled based on the input status
Step
Default
1=on
10000
30000
1
200
Section 8
Control functions
Description
Operation mode on/off
Select timeout in ms
Open and close pulse length
1)2)
1)2)
221