1MRS758407 B
7.1.5.5
SMU615
Technical Manual

Monitored data

Table 218:
VMMXU Monitored data
Name
Type
U12-kV
FLOAT32
U23-kV
FLOAT32
U31-kV
FLOAT32
BLOCK
BOOLEAN
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
U_INST_AB
FLOAT32
U_ANGL_AB
FLOAT32
U_DB_AB
FLOAT32
U_DMD_AB
FLOAT32
U_RANGE_AB
Enum
U_INST_BC
FLOAT32
U_ANGL_BC
FLOAT32
U_DB_BC
FLOAT32
U_DMD_BC
FLOAT32
U_RANGE_BC
Enum
Table continues on next page
Measurement functions
Values (Range)
Unit
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0.00...4.00
xUn
-180.00...180.00
deg
0.00...4.00
xUn
0.00...4.00
xUn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...4.00
xUn
-180.00...180.00
deg
0.00...4.00
xUn
0.00...4.00
xUn
0=normal
1=high
2=low
3=high-high
4=low-low
Section 7
Description
Measured phase to
phase voltage amplitude
phase AB
Measured phase to
phase voltage amplitude
phase BC
Measured phase to
phase voltage amplitude
phase CA
Block signal for all binary
outputs
High alarm
High warning
Low warning
Low alarm
U12 Amplitude,
magnitude of
instantaneous value
U12 angle
U12 Amplitude,
magnitude of reported
value
Demand value of U12
voltage
U12 Amplitude range
U23 Amplitude,
magnitude of
instantaneous value
U23 angle
U23 Amplitude,
magnitude of reported
value
Demand value of U23
voltage
U23 Amplitude range