Parameter group Ventilation

7D72 Control voltage matching, exhaust air fan

Vitovent
200-C
200-W
300-C
X
To compensate for any pressure differential between
the supply air and extract air side, the speed of the
exhaust air fan compared to the supply air fan can be
raised or lowered. To do so the value set here is added
permanently to the control voltage of the exhaust air
fan.
7D75 Sensor matching, outdoor air temperature
Vitovent
200-C
200-W
300-C
X
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the outdoor air temperature sensor.
7D76 Sensor matching, outdoor air temp after preheating coil
Vitovent
200-C
200-W
300-C
X
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the outdoor air temperature sensor.
7D77 Sensor matching, supply air temperature
Vitovent
200-C
200-W
300-C
X
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the supply air temperature sensor.
7D79 Sensor matching, extract air temperature
Vitovent
200-C
200-W
300-C
X
258
300-F
300-W
300-F
300-W
300-F
300-W
300-F
300-W
300-F
300-W
!
Setting 1
0.01 V
!
Recommendation:
Set "Standby mode" for the ventilation unit. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1
0.1 K
!
Recommendation:
Set "Standby mode" for the ventilation unit. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1
0.1 K
!
Recommendation:
Set "Standby mode" for the ventilation unit. After
some time, compare the temperature values of all tem-
perature sensors against each other and/or against a
reference temperature. Set a corresponding correction
value for any deviating temperature sensors.
Setting 1
0.1 K
!
To compensate for systematic measuring errors, a
positive or negative adjustment value (offset) can be
set for the extract air temperature sensor.