Viessmann VITOTRONIC 200 Service Instructions Manual page 166

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
0A
Short circuit/lead break,
S
low pressure sensor (suc-
tion gas pressure sensor)
0E
Short circuit/lead break,
S
liquid gas temperature
sensor
10
Compressor switched off
H
13
Vitocal 333-G:
S
Communication error
15
Vitocal 333-G:
S
Inverter and compressor
incompatible
18
Vitocal 333-G:
S
Compressor fault (general
message)
1A
Safety chain interrupted,
S
compressor blocked
1E
EEV PCB faulty
S
1F
Parameter "Output com-
pressor stage 5030" not
set correctly
20
Condensing pressure too
H
high (control high pres-
sure)
21
Inadequate evaporation
H
pressure (low pressure
fault)
22
Excessively high hot gas
H
temperature
24
Compressor failed to start:
S
Message "88" has occur-
red 3 times successively.
29
Condensing temperature
H
too high
2B
Max. suction gas pressure
H
exceeded
166
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Subject to other messages
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Measure
Check current at connection J10 (P1)
of the EEV PCB: See "EEV PCB
[4-6] / [4-7]". Take refrigerant R410A
into account.
Check resistance value (NTC 10 k
at connection J13 (T7) of the EEV
PCB: See "EEV PCB [4-6] / [4-7]".
No action required
Check Modbus connecting cable, in-
verter
EEV PCB.
Check the DIP switches on the EEV
PCB are set correctly. Observe label
for correct setting.
See further messages regarding the
compressor and inverter (message
code "80" and above).
Check safety chain: See connection
and wiring diagram.
Check plug for compressor controller
on the EEV PCB: See "EEV PCB
[4-6] / [4-7]".
Replace EEV PCB.
Set "Output compressor stage
5030" according to the type plate.
Then switch off the heat pump control
unit. Wait 1 min. Then restart the heat
pump control unit.
As for "D4 Control high pressure":
See "Message overview" for the heat
pump control unit.
As for "D3 Low pressure": See "Mes-
sage overview" for the heat pump con-
trol unit.
Have a specialist check the com-
pressor parameters ("5xxx").
Check whether the coding card
matches the heat pump. To check in-
formation, see "System information".
Check compressor drive.
Vitocal 333-G:
Check inverter.
As for "D4 Control high pressure":
See "Message overview" for the heat
pump control unit.
Check amount of refrigerant. Adjust
amount if required.
If fault persists, notify a specialist.
)