Configuring the solar control module

The solar control module is recognised as a KM BUS
subscriber automatically by the heat generator control
unit (coding address 54).
The relevant codes for the solar control module are set
at the heat generator control unit.
Vitotronic control units for oil and gas boilers
Weather-compensated control:
Select group "Solar".
Constant temperature control:
Select group "4".
Vitotronic control units for heat pumps (type
WO1C)
Select parameter group "Solar".
In the "Type solar control unit 7A00" parameter,
select value 3.
Invoke parameter "C0xx".
For the final two characters (xx), enter the desired
coding address from the following table.

Coding addresses overview

Coding

Coding in the delivered condition
Start point, solar circuit pump
00:8
Start temperature differential for
solar circuit pump 8 K.
Stop point, solar circuit pump
01:4
Stop temperature differential for
solar circuit pump 4 K.
Speed control, solar circuit pump
02:0
Solar circuit pump is not speed-
controlled
Differential temperature, speed control
03:10
Temperature differential for the
start of the speed control 10 K.
Controller amplification, speed control
04:4
Controller amplification of the
speed control 4 %/K.
Minimum speed, solar circuit pump
05:10
Min. speed of the solar circuit
pump 10 % of maximum speed.
06:75
Max. speed of the solar circuit
pump 75 % of the maximum possi-
ble speed.
Service instructions for the heat source or con-
trol unit
For the required codes, see the selected system
example.
For a function description and further details on the
coding addresses, see page 18.
Possible change
00:2
Start temperature differential adjust-
to
able from 2 to 30 K.
00:30
01:1
Stop temperature differential adjust-
to
able from 1 to 29 K.
01:29
02:1
Solar circuit pump is speed-control-
led with wave packet control
02:2
Solar circuit pump is speed-control-
led with PWM control
03:5
Temperature differential adjustable
to
from 5 to 20 K.
03:20
04:1
Controller amplification adjustable
to
from 1 to 10 %/K.
04:10
05:2
Min. speed of the solar circuit pump
to
adjustable from 2 to 100 %.
05:100
06:1
Max. speed of the solar circuit pump
to
adjustable from 1 to 100 %.
06:100
Commissioning
9