Viessmann VITOTRONIC 200 Service Instructions Manual page 158

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
95
Discharge current at IGBT
H
too high
96
Precharge relay open
H
97
Voltage difference of indi-
H
vidual phases too high
(> 50 %)
98
Voltage difference of indi-
H
vidual phases too high
(> 5 A)
99
Current difference of pow-
H
er factor correction filter
too high (> 10 A)
9A
Supply voltage of inverter
H
control outside of voltage
range
9B
Temperature of power fac-
H
tor correction filter too
high
9C
Outside temperature too
H
low
9D
Temperature differential of
H
phase controls too high
9F
More than 10 messages
H
have occurred
B0
Fan communication fault
S
B1
Fan motor overheats
S
B2
Fan motor speed monitor
S
faulty
B3
Fan motor blocked
S
B4
Fan motor supply voltage
S
too low
158
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Fan off, compressor re-
mains in operation.
Fan off, compressor re-
mains in operation.
Fan off, compressor re-
mains in operation.
Fan off, compressor re-
mains in operation.
Fan off, compressor re-
mains in operation.
Measure
Replace inverter.
Test coil resistance at compressor.
Resistance on all windings must be
similar (
10 %). For m
±
Ω
ble measuring device.
Replace inverter if necessary.
No action required
Test coil resistance at compressor.
Resistance on all windings must be
similar (
10 %). For m
±
Ω
ble measuring device.
Replace inverter if necessary.
Inverter is automatically reset. If mes-
sage continues to be displayed, reset
inverter in "Actuator test".
Check plug at connection J19: See
"EEV PCB [4]".
Check luster terminals in the heat
pump terminal area if necessary.
Replace motor if it is mechanically
sluggish in its movement.
If the motor turns easily, notify a spe-
cialist.
Check electrical connection of fan in
heat pump terminal area.
Replace fan motor if necessary.
If fault persists, notify a specialist.
If motor is mechanically sluggish, re-
move blockage. Replace motor if
necessary.
If the motor turns easily, notify a spe-
cialist.
Check electrical connection of fan in
heat pump terminal area.
Replace fan motor if necessary.
If fault persists, notify a specialist.
use a suita-
use a suita-