Energy Statement - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
97
Voltage difference of indi-
H
vidual phases too high
(> 50 %)
99
Current difference of pow-
H
er factor correction filter
too high (> 10 A)
9B
Temperature of power fac-
H
tor correction filter too
high
9D
Temperature differential of
H
phase controls too high
9E
Voltage at inverter too low Compressor OFF
S
9F
More than 3 messages
H
occurred within 1 h
B3
Fan motor blocked
S
C0
Inverter reset
S
C1
Current capture fault, in-
S
verter
C2
Phase reversal, inverter
S
C3
Fault, load circuit, inverter
S

Energy statement

Note
The "Energy statement" will only be displayed if
"User level for display, energy stmt 8811" is set to
"1" or "2".
Prerequisite for recording realistic data:
Parameter "Output compressor stage 5030" is set
correctly.
178
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor off: Message
"A9 Heat pump" is shown.
Fan off, compressor re-
mains in operation.
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Measure
Check the compressor connecting
cable. Replace the connecting cable
if necessary.
!
Please note
400 V appliances: An incor-
rect rotating field will irrepara-
bly damage the compressor.
When replacing the connect-
ing cable, ensure the phases
are connected correctly.
Replace inverter if required.
Replace inverter.
Test coil resistance at compressor.
Resistance on all windings must be
similar (
10 %). For m
±
Ω
ble measuring device.
Replace inverter if required.
Test coil resistance at compressor.
Resistance on all windings must be
similar (
10 %). For m
±
Ω
ble measuring device.
Replace inverter if required.
No action required; automatic reset of
compressor
As for "A9 Heat pump": See "Mes-
sage overview" for the heat pump con-
trol unit.
If motor is mechanically sluggish, re-
move blockage. Replace motor if
necessary.
If the motor turns easily, notify a spe-
cialist.
No action required: Compressor is au-
tomatically reset.
Replace inverter.
Connect inverter with correct phases.
Replace inverter.
use a suita-
use a suita-