C10B Standard Ventilation - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

C10B Standard ventilation

Vitovent
200-C
200-W
300-C
X
Set air flow rate for the "Standard" operating status in
the ventilation time program (ventilation level
Set the design flow rate from planning here.
Note for Vitovent 200-W
This setting only applies to the supply air flow rate.
The set extract air flow rate is set with "Standard ven-
tilation, second fan duct C18B". Pressure imbalan-
ces in the ductwork can be balanced out with different
settings for the supply air and extract air flow rates.
C10C Intensive ventilation
Vitovent
200-C
200-W
300-C
X
Set air flow rate for the "Intensive" operating status in
the ventilation time program (ventilation level
Setting subject to the building and engineering.
Standard setting values:
In the middle, between "Standard ventilation
C10B" and the max. air flow rate
Max. air flow rate
Installation and service instructions for the
connected ventilation unit
or
Approx. 30 % higher than "Standard ventilation
C10B"
C189 Background ventilation, second fan duct
Vitovent
200-C
200-W
300-C
X
Set air flow rate for "Economy mode", "Standard
operation" and "Holiday program" (ventilation level
).
1
Setting subject to the building and engineering.
Standard setting value:
3
Centrally between 0 m
/h and "Reduced ventila-
tion, second fan duct C18A"
or
Approx. 30 % lower than "Reduced ventilation,
second fan duct C18A"
!
300-F
300-W
X
X
).
3
!
300-F
300-W
X
X
).
4
300-F
300-W
Parameter group Ventilation
Vitovent 200-W: Setting in % in accordance with fan
curves
Fan curves
Installation and service instructions
"Vitovent 200-W"
Vitovent 300-C/300-W: Setting in m
Note for Vitovent 200-W
This setting only applies to the supply air flow rate.
The set extract air flow rate is set with "Intensive ven-
tilation, second fan duct C18C". Pressure imbalan-
ces in the ductwork can be balanced out with different
settings for the supply air and extract air flow rates.
Vitovent 200-W: Setting in % in accordance with fan
curves
Fan curves
Installation and service instructions
"Vitovent 200-W"
Vitovent 300-C/300-W: Setting in m
!
Note
The set supply air flow rate is set with "Background
ventilation C109". Pressure imbalances in the duct-
work can be balanced out with different settings for the
supply air and extract air flow rates.
Setting in % in accordance with fan curves
Fan curves
Installation and service instructions
"Vitovent 200-W"
3
/h
3
/h
261