Function check
(cont.)
Function
"Heating circuit 1"
"Heating circuit 2"
"Heating circuit 3"
"Cooling circuit SKK"
"DHW" (DHW cylinder)
"Swimming pool"
"Electr booster heater" (instantane-
ous heating water heater)
"STB Electr booster heater"
"Heat pump"
"Defrost"
/
"External heat pump"
"External heat source"
With solar control module, type SM1:
"Solar"
System characteristics
Secondary pump and heating circuit pump for heating/cooling circuit
A1/HC1 are started.
Heating circuit pump for heating/cooling circuit M2/HC2 or M3/HC3 is
■
started.
Mixer for heating/cooling circuit M2/HC2 or M3/HC3 opens/closes ev-
■
ery 5 min.
:
Primary pump and circulation pump in separate cooling circuit are star-
■
ted.
Mixer for NC function opens/closes every 5 min. NC signal is activa-
■
ted.
/ :
4-way diverter valve switches over.
■
Separate cooling circuit circulation pump is started.
■
The following components are started or changed over:
Secondary pump
■
3-way diverter valve "Central heating/DHW heating"
■
Cylinder loading pump (DHW side)
■
Secondary pump starts.
■
Circulation pump for swimming pool heating and 3-way diverter valve
■
are switched on/off every minute.
Secondary pump starts.
■
When the minimum flow rate has been reached, stage 1 of the instan-
■
taneous heating water heater is started.
Stage 2 and stage 3 of the instantaneous heating water heater are
■
started at 30 s intervals.
The instantaneous heating water heater regulates to a flow tempera-
■
ture of 30 °C.
Stage 3 of the instantaneous heating water heater is switched on.
■
The secondary pump is not switched on.
■
The high limit safety cut-out must respond as soon as the temperature at
the sensor of the capillary tube reaches 85
High limit safety cut-out has responded:
■
The instantaneous heating water heater does not start with the "Electr
booster heater" function. The secondary circuit flow temperature
does not rise.
High limit safety cut-out has not responded:
■
The instantaneous heating water heater starts with the "Electr boos-
ter heater" function. The secondary circuit flow temperature rises.
Secondary pump and primary pump/fan of outdoor unit start.
■
Compressor regulates to the set value. Compressor output is set.
■
Secondary circuit regulates to a return temperature of 30 °C.
■
The defrost function starts.
■
The process ends if the evaporator temperature reaches the stop val-
■
ue.
All lag heat pumps are started for heating mode and regulated to a re-
turn temperature of 30 °C in the secondary circuit.
The external heat generator is regulated to a flow temperature of
■
35 °C.
External heat generator mixer opens.
■
Heating circuit pumps are started.
■
Solar circuit pump starts.
Service functions
8
–
°C.
189