Viessmann VITOTRONIC 200 Service Instructions Manual page 298

Heat pump control unit
Table of Contents

Advertisement

PCBs and connection options
Luster terminals Vitocal 200-A
Terminals
Function
X3.8
Frost stat and/or contact humidistat
X3.9
or
Jumper
X3.18
Heat pump control unit power supply:
Phase L1
X1.1 Earth conductor connection
X2.1 Neutral conductor connection
298
(cont.)
Explanation
Note
No parameters need to be set
No jumper should be installed if a power-OFF contact
is connected.
The compressor is "forced" off as soon as the contact
opens.
The power-OFF signal switches off the supply voltage
of the respective operating component (subject to the
power supply utility).
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
(3 x 1.5 mm
can be combined in a single 5-core cable.
In connection with Smart Grid:
The power-OFF signal must not be connected.
Jumper must be fitted.
Requires floating contact:
Closed: Safety chain has continuity
Open: Safety chain interrupted; heat pump shut down
Breaking capacity 230 V~, 0.15 A
Connected in series if both safety components are in-
stalled
Insert jumper if no safety components are instal-
led.
Power supply 230 V~
2
) and the cable for the power-OFF signal