Viessmann VITOTRONIC 200 Service Instructions Manual page 156

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
4C
Suction gas superheating
too high
55
Too little refrigerant
H
Electronic expansion
valve for suction gas
fully open
56
H
Condenser frost risk
57
Electronic expansion
H
valve for refrigerant collec-
tor level control fully open
58
Liquid gas supercooling
too high
59
Electronic expansion
S
valve for suction gas su-
perheating faulty
5A
Electronic expansion
S
valve for refrigerant collec-
tor level control faulty
5B
Charge level in refrigerant
collector too low
5D
Insufficient hot gas super-
H
heating
65
Charge level sensor of re-
S
frigerant collector faulty
156
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Refrigerant circuit rever-
sal OFF
Compressor OFF
Compressor remains in op-
eration.
Compressor OFF
Compressor OFF
Compressor remains in op-
eration.
Compressor OFF
Compressor remains in op-
eration.
Measure
Check whether the correct coding
card is fitted. To check information,
see "System information".
In the event of recurrence: Have the
refrigerant circuit checked by a re-
frigeration engineer.
Check amount of refrigerant. Adjust
if necessary.
Check plug at connection J11: See
"EEV PCB [4]".
Check stepper motor of electronic
expansion valve.
Check hydraulics in the secondary
circuit, e.g. whether all shut-off
valves are fully open.
Check secondary circuit flow rate.
Check flow and return temperature
in the secondary circuit.
Check flow and return temperature
sensor in the secondary circuit.
Check amount of refrigerant. Adjust
if necessary.
Check temperature sensors in the
refrigerant circuit.
Check plug at connection J7: See
"EEV PCB [4]".
Check stepper motor of electronic
expansion valve.
Check secondary circuit flow rate. If
necessary, increase the flow rate.
Check installation position of the liq-
uid gas temperature sensor: See "In-
ternal components".
Check resistance value (NTC 10 k
at connection J13 (T5) on the EEV
PCB: See "EEV PCB [4]".
Check plug at connection J11: See
"EEV PCB [4]".
Check stepper motor of electronic
expansion valve.
Check plug at connection J7: See
"EEV PCB [4]".
Check stepper motor of electronic
expansion valve.
Reduce set flow temperature for sec-
ondary circuit, e.g. by adjusting the
heating curves.
Check hot gas temperature sensor:
See message code "0E".
Check plug at connection J25/J26:
See "EEV PCB [4]". Replace sensor if
necessary.
)