Viessmann VITOTRONIC 200 Service Instructions Manual page 285

Heat pump control unit
Table of Contents

Advertisement

Main and expansion PCB
Plug
sXS
Terminals
Function
222.1
/
Control of mixer motor for external
heat generator
Signal mixer CLOSE
222.2
/
Control of mixer motor for external
heat generator
Signal mixer OPEN
222.3
/
222.4
Control of external heat generators
and 1 high limit safety cut-out each
(on site, max. 70 °C), to switch off or
switch between the following compo-
nents:
Central heating:
Secondary pump, heat pump
External heat generator
DHW reheating:
3-way diverter valve "Central heat-
ing/DHW heating"
Plug
sXD
Terminals
Function
223.1
Central fault message
223.2
U
Plug
sXF
Terminals
Function
224.4
Instantaneous heating water heater
switching, stage 2.
2.
r
224.6
:
Cylinder loading pump (DHW side)
:
2-way shut-off valve
M
(cont.)
:
:
:
PCBs and connection options
Explanation
Connection values
Output: 10 W
Voltage: 230 V~
Max. switching current: 0.2(0.1) A
Connection values
Output: 10 W
Voltage: 230 V~
Max. switching current: 0.2(0.1) A
Floating contact
Connection values (contact load)
Voltage: 230 V~
(not suitable for safety LV)
Max. switching current: 4(2) A
Connections for high limit safety cut-outs
Central heating:
In series to the secondary pump (terminal 211.2 on
the main PCB)
In series for controlling the external heat generator
(terminal 222.3)
DHW reheating:
In series to 3-way diverter valve "Central
heating/DHW heating" (terminal 211.4 on the main
PCB)
Explanation
Floating contact:
Closed: Fault
Open: No fault
Not suitable for safety LV
Connection values (contact load)
Voltage: 230 V~
Max. switching current: 4(2) A
Explanation
Connection values
Output: 10 W
Voltage: 230 V~
Max. switching current: 4(2) A
Connect cylinder loading pump and 2-way shut-off
valve in parallel.
Connection values
Output: 130 W
Voltage: 230 V~
Max. switching current: 4(2) A
285