Diagnosis
Refrigerant circuit
Message
Meaning
code
99
Vitocal 333-G:
H
Current difference of the
individual phases on the
compressor too high
9B
Vitocal 333-G:
H
Temperature of power fac-
tor correction filter too
high
9E
Vitocal 333-G:
S
1 phase of inverter supply
voltage missing.
A0
Vitocal 333-G:
S
Current sensor phase L1
of compressor supply volt-
age faulty
A1
Vitocal 333-G:
S
Current sensor phase L2
of compressor supply volt-
age faulty
A2
Vitocal 333-G:
S
Current sensor phase L3
of compressor supply volt-
age faulty
A3
Vitocal 333-G:
S
Current sensor power fac-
tor correction filter faulty
A4
Vitocal 333-G:
S
Temperature sensor, in-
verter (IGBT module) faul-
ty
A5
Vitocal 333-G:
S
Temperature sensor pow-
er factor correction filter
faulty
170
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Measure
Check connecting cable from inverter
compressor. Replace the connect-
ing cable if necessary: See "Connec-
tion and wiring diagram".
!
Please note
400 V appliances: An incorrect
rotating field will irreparably
damage the compressor.
When replacing the connecting
cable, ensure the phases are
connected correctly.
Test coil resistance at compressor.
Resistance on all windings should
be similar (
10 %). Use measuring
±
device suitable for m
.
Ω
Replace inverter if required.
Check inverter power supply.
Replace inverter.