Diagnosis
Refrigerant circuit
Message
Meaning
code
99
Vitocal 333-G:
H
Current difference of the
individual phases on the
compressor too high
9B
Vitocal 333-G:
H
Temperature of power fac-
tor correction filter too
high
9E
Vitocal 333-G:
S
1 phase of inverter supply
voltage missing.
A0
Vitocal 333-G:
S
Current sensor phase L1
of compressor supply volt-
age faulty
A1
Vitocal 333-G:
S
Current sensor phase L2
of compressor supply volt-
age faulty
A2
Vitocal 333-G:
S
Current sensor phase L3
of compressor supply volt-
age faulty
A3
Vitocal 333-G:
S
Current sensor power fac-
tor correction filter faulty
A4
Vitocal 333-G:
S
Temperature sensor, in-
verter (IGBT module) faul-
ty
A5
Vitocal 333-G:
S
Temperature sensor pow-
er factor correction filter
faulty
170
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Measure
Check connecting cable from inverter
compressor. Replace the connect-
—
ing cable if necessary: See "Connec-
tion and wiring diagram".
!
Please note
400 V appliances: An incorrect
rotating field will irreparably
damage the compressor.
When replacing the connecting
cable, ensure the phases are
connected correctly.
Test coil resistance at compressor.
■
Resistance on all windings should
be similar (
10 %). Use measuring
±
device suitable for m
.
Ω
Replace inverter if required.
■
Check inverter power supply.
Replace inverter.