Viessmann VITOTRONIC 200 Service Instructions Manual page 161

Heat pump control unit
Table of Contents

Advertisement

Refrigerant circuit
(cont.)
Message
Meaning
code
3A
Safety high pressure
S
switch has responded.
43
Short circuit/lead break,
S
temperature sensor, refrig-
erant circuit controller
44
Short circuit/lead break,
S
secondary circuit flow
temperature sensor (up-
stream of instantaneous
heating water heater)
46
Short circuit/lead break,
S
liquid gas temperature
sensor
47
Short circuit/lead break,
S
reversible suction gas
temperature sensor
48
Suction gas superheating
too low
49
Evaporator max. operating
pressure (MOP) has been
reached; changeover from
superheating to pressure
control of the suction gas.
4C
Suction gas superheating
too high
55
Too little refrigerant
H
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor remains in op-
eration.
Compressor OFF
Compressor OFF
Measure
As for "C9 Refrigerant circ (SHD)":
See "Message overview" for the heat
pump control unit.
Check resistance value (NTC 10 k
at connection J21 (T2) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Vitocal 200-A/222-A:
Check resistance value (NTC 10 k
at connection J21 (T1) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Vitocal 200-S/222-S:
Check resistance value (Pt500A) at
connection X25.3/X25.4 of the con-
troller and sensor PCB: See "Con-
troller and sensor PCB".
Vitocal 200-A/222-A:
Check resistance value (NTC 10 k
at connection J21 (T3) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Vitocal 200-S/222-S:
Check resistance value (Pt500A) at
connection F25 (X25.17/X25.18) of
the controller and sensor PCB: See
"Controller and sensor PCB".
Check resistance value (Pt500A) at
connection X25.15/X25.16 of the con-
troller and sensor PCB: See "Control-
ler and sensor PCB".
Check whether the correct coding
card is fitted. To check information,
see "System information".
In the event of recurrence: Have the
refrigerant circuit checked by a re-
frigeration engineer.
No action required
Check whether the correct coding
card is fitted. To check information,
see "System information".
In the event of recurrence: Have the
refrigerant circuit checked by a re-
frigeration engineer.
Check amount of refrigerant. Adjust
the amount of refrigerant if necessary.
Diagnosis
)
Ω
)
Ω
)
Ω
161