Viessmann VITOTRONIC 200 Service Instructions Manual page 159

Heat pump control unit
Table of Contents

Advertisement

Refrigerant circuit
(cont.)
Message history
For refrigerant circuit controller [4-3] / [4-4]: For differ-
entiating between the refrigerant circuit controllers, see
chapter "System information".
Message history of the refrigerant circuit controller
(status and fault information):
Messages cannot be acknowledged in the message
history.
Messages are listed in chronological order. The most
recent message is listed first.
Up to 30 entries are stored.
1. Service menu:
Press OK +
simultaneously and hold for
å
approx. 4 s.
2. "Diagnosis"
3. "Refrigerant circuit"
4. "Message history"
Message overview
Note
Some faults should only be remedied by a (specialist)
heating contractor certified for heat pumps by
Viessmann.
Message
Meaning
code
01
Short circuit/lead break,
S
primary circuit flow tem-
perature sensor (heat
pump air intake)
03
Short circuit/lead break,
S
suction gas temperature
sensor
04
Short circuit/lead break,
S
hot gas temperature sen-
sor
05
Short circuit/lead break,
S
high pressure sensor (liq-
uid gas pressure sensor)
0A
Short circuit/lead break,
S
low pressure sensor (suc-
tion gas pressure sensor)
[4-3] / [4-4]
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
A
B
Message history
0 09.09.2009 17:16:00
1
09.09.2009 17:16:01
2
09.09.2009 17:16:02
3
09.09.2009 17:16:03
Back with
Fig. 36
Message number
A
Date and time of the last occurrence
B
2-digit message code
C
Type of message: "Note" or "Fault"
D
Frequency of occurrence
E
Refrigerant circuit controller messages can trigger a
message at the heat pump control unit (see "Message
overview"). Which message will be triggered at the
heat pump control unit depends on the type of mes-
sage at the refrigerant circuit controller.
Type of message at
Message at heat pump con-
refrigerant circuit
trol unit
controller
H
"Note"
"07 Message refrig. circ"
"Fault"
"05 Fault refrigerant circ"
S
Measure
Check resistance value (NTC 10 k
at connection J13 (T5) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Check resistance value (NTC 10 k
at connection J13 (T4) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Check resistance value (NTC 10 k
at connection J13 (T6) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
Check current at connection J10 (P2)
of the EEV PCB: See "EEV PCB
[4-3] / [4-4]". Take refrigerant R410A
into account.
Check current at connection J10 (P1)
of the EEV PCB: See "EEV PCB
[4-3] / [4-4]". Take refrigerant R410A
into account.
Diagnosis
C
D
E
06 Fault
7
Fault
0A
3
03 Note
11
10
Fault
1
)
Ω
)
Ω
)
Ω
159