Viessmann VITOTRONIC 200 Service Instructions Manual page 290

Heat pump control unit
Table of Contents

Advertisement

PCBs and connection options
Vitocal 300-A cross connect PCB
Terminals
Function
X3.1, X3.2,
Switched phase
X3.3, X3.7,
X3.11, X3.13,
X3.16
X3.2
"External blocking" signal: External
X3.14
blocking of compressor and pumps,
mixer in control mode or CLOSE
X3.3
Flow switch, secondary circuit
X3.4
X3.6
Power-OFF
X3.7
G
290
(cont.)
Explanation
Note
Observe the total load of 1000 W for all connected
components.
Requires floating contact:
Closed: Blocking active
Open: No blocking
Breaking capacity 230 V~, 2 mA
Note
These and further external functions (such as provi-
sion of external set values) can alternatively be con-
nected via the external EA1 extension (not in con-
junction with Smart Grid).
"EA1 extension" installation instructions
Requires floating contact:
Closed: Heat pump operational
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Jumper is used in some devices.
No jumper should be installed if a flow switch is con-
nected.
Requires floating contact:
Closed: No blocking (safety chain continuous)
Open: Blocking active
Breaking capacity 230 V~, 0.15 A
Note
No parameters need to be set
No jumper should be installed if a power-OFF contact
is connected.
The compressor is "forced" off as soon as the contact
opens.
The power-OFF signal switches off the supply voltage
of the respective component (subject to the power
supply utility).
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
(3 x 1.5 mm
can be combined in a single 5-core cable.
In connection with Smart Grid:
The power-OFF signal must not be connected.
Jumper must be installed.
2
) and the cable for the power-OFF signal