Adjusting The Air Flow Rates; Balancing The Supply Air/Extract Air Flow Rates - Viessmann LB1 Installation And Service Instructions For Contractors

Ventilation programming unit programming unit for mechanical ventilation systems with heat recovery
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Setting air flow rates
Setting the air flow rates for Vitovent 200-C
1. Service menu:
Press OK +
simultaneously and hold for
å
approx. 4 s.
2. "Parameter level 1"
Setting the air flow rates for Vitovent 300-C/300-W
1. Service menu:
Press OK +
simultaneously and hold for
å
approx. 4 s.
2. "Parameter level 1"

Adjusting the air flow rates

"Air distribution systems" installation and service
instructions

Balancing the supply air/extract air flow rates

Note
Balancing is only required if the total of the actual air
flow rates of all supply air apertures deviates by more
than 10 % from that of all extract air apertures.
Vitovent 200-C
To balance out the air flow rate differentials, the control
voltages of the supply and/or exhaust air fan can be
permanently increased or reduced.
1. Service menu:
Press OK +
simultaneously and hold for
å
approx. 4 s.
Vitovent 300-C
1. Service menu:
Press OK +
simultaneously and hold for
å
approx. 4 s.
2. "Parameter level 1"
3. Set "Imbalance permitted C1A2" to "1".
16
(cont.)
3. Set the air flow rates using the following parame-
ters:
"7D0A Flow rate, reduced ventilation"
"7D0B Flow rate, nominal ventilation"
"7D0C Flow rate, intensive ventilation"
Note
For Vitovent 200-C, the air flow rate for "Back-
ground vent." is set at the factory to 50 m
cannot be adjusted.
3. Set the air flow rates using the following parame-
ters:
"C109 Background ventilation"
"C10A Reduced ventilation"
"C10B Standard ventilation"
"C10C Intensive ventilation"
2. "Parameter level 1"
3. Set the control voltages:
"Control voltage matching, supply air fan
7D71"
"Control voltage matching, exhaust air fan
7D72"
4. An increase or decrease in the supply air flow rate
in comparison to the extract air flow rate can be set
with "Specified imbalance C1A3".
3
/h and