Viessmann VITOTRONIC 200 Service Instructions Manual page 149

Heat pump control unit
Table of Contents

Advertisement

Refrigerant circuit
(cont.)
Type of message at
Message at heat pump con-
refrigerant circuit
trol unit
controller
"Note"
"07 Fault refrigerant circ"
H
"Fault"
"05 Fault refrigerant circ"
S
Message
Meaning
code
00
No message
01
Short circuit/lead break,
S
air intake temperature
sensor
02
Short circuit/lead break,
S
air discharge temperature
sensor
03
Short circuit/lead break
S
suction gas temperature
sensor
04
Short circuit/lead break,
S
hot gas temperature sen-
sor
05
Short circuit/lead break,
S
high pressure sensor
06
Short circuit/lead break
S
liquid gas temperature
sensor 1 (upstream of the
EEV)
07
Short circuit/lead break
S
liquid gas temperature
sensor 2 (downstream of
the EEV)
08
Short circuit/lead break,
S
return temperature sensor,
secondary circuit
09
Short circuit/lead break
S
evaporator temperature
sensor
0A
Short circuit/lead break,
S
low pressure sensor
10/11
Compressor has stopped.
H
12
Inverter fault (general
message)
15
Inverter and compressor
S
incompatible
Heat pump characteris-
tics
Operation with temperature
value of return temperature
sensor in primary circuit,
plus 3 K
Operation with temperature
value of flow temperature
sensor in primary circuit,
minus 2 K
Compressor OFF
Compressor remains in
operation.
Energy statement is not
calculated correctly: See
chapter "Diagnosis, ener-
gy statement".
Compressor remains in
operation.
Energy statement is not
calculated correctly: See
chapter "Diagnosis, ener-
gy statement".
Operation with temperature
value of flow temperature
sensor in secondary circuit,
minus 5 K
Compressor may stop due
to a change in refrigerant
circuit conditions.
Compressor OFF
Subject to other messages
Compressor OFF
Measure
Check resistance value (Pt500A) at
the sensor connection of the EEV
PCB: See "EEV PCB [2]".
Check resistance value (Pt500A) at
the sensor connection of the EEV
PCB: See "EEV PCB [2]".
Test voltage at the high pressure sen-
sor connection: See "EEV PCB [2]".
0.5 V: 0 bar
4.5 V: Max. pressure, see sensor im-
print.
Check resistance value (Pt500A) at
the sensor connection of the EEV
PCB: See "EEV PCB [2]".
Test voltage at the low pressure sen-
sor connection: See "EEV PCB [2]".
0.5 V: 0 bar
4.5 V: Max. pressure, see sensor im-
print.
No action required
Observe other messages relating to
the inverter (message codes "80" to
"93").
Check whether the coding card match-
es the heat pump. To check informa-
tion, see "System information".
Diagnosis
149