Viessmann VITOTRONIC 200 Service Instructions Manual page 133

Heat pump control unit
Table of Contents

Advertisement

Ventilation
(cont.)
Type of message at
Message on the heat pump
the ventilation unit
control unit
"Note"
"0F Ventilation unit"
H
"Warning"
"A0 Vent.: check filter(s)"
W
"Fault"
"0E Ventilation unit"
S
Message
Meaning
code
01
Only Vitovent 300-F:
W
Differential pressure has
02
W
exceeded response value
of one or both differential
pressure switches.
03
Time interval for filter
W
change has expired.
05
Short circuit/lead break,
S
outdoor air temperature
sensor
06
Short circuit/lead break,
S
supply air temperature
sensor
07
Short circuit/lead break,
S
extract air temperature
sensor
08
Only Vitovent 300-F:
S
Short circuit/lead break,
exhaust air temperature
sensor
09
Only Vitovent 300-F:
S
CO
signal capture disrup-
2
ted
0A
Only Vitovent 300-F:
S
Humidity signal capture
disrupted
0C
Only Vitovent 300-F:
Air humidity has exceeded
the limit for raising the air
flow rate.
0D
Only Vitovent 300-F:
CO
concentration has ex-
2
ceeded the limit for raising
the air flow rate.
0E
"Standard operation"
H
was activated due to an-
other fault, e.g. sensor
fault. Message does not
occur on its own.
Ventilation unit character-
istics
Ventilation unit remains op-
erational, increased electri-
cal power consumption.
Vitovent 200-C: Ventila-
tion unit is switched off.
Vitovent 300-F: "Stand-
ard operation" is being
activated. The value of
the exhaust air tempera-
ture sensor minus 5 K is
used.
Vitovent 200-C: Ventila-
tion unit is switched off.
Vitovent 300-F: "Stand-
ard operation" is switch-
ed on.
"Standard operation" is
being activated. The value
of the outdoor air tempera-
ture sensor is used.
Ventilation unit remains op-
erational, no regulation of
the CO
concentration.
2
Ventilation unit remains op-
erational, no regulation of
the humidity.
Air flow rate is raised.
"Standard operation" is
being activated.
Bypass blocked.
Measure
Replace outdoor air and extract air fil-
ters. Reset maintenance display.
Check resistance value (NTC 10 k
of ventilation unit sensor: See installa-
tion and service instructions for the
ventilation unit.
Check CO
/humidity sensor.
2
No action required
Measures according to the other mes-
sages
Diagnosis
)
Ω
133