D1B Intensive Ventilation Duration - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Parameter group Ventilation

7D1B Intensive ventilation duration

Vitovent
200-C
200-W
300-C
X
After expiry of the set duration, if "Intensive opera-
tion" is set at the heat pump control unit, the control
unit automatically restarts the last selected function or
the last selected operating program, e.g. "Ventilation
program".
7D1D Actual source room temperature
Vitovent
200-C
200-W
300-C
Room temperature sensor for supply air heating via
ventilation heating circuit A1/HC1 ("Enable reheater
bank hydraulic 7D02" set to "1").
The room temperature sensor is required in the follow-
ing cases:
Weather-compensated control unit with room tem-
perature hook-up ("Room temperature hook-up
200B" set to "1", "2" or "3")
Room temperature-dependent control unit
7D21 Heating circuit for blocking bypass damper
Vitovent
200-C
200-W
300-C
X
X
With central heating via the set heating circuit, the
bypass is not activated for passive cooling.
This prevents the heat supplied via the heating cir-
cuit being routed outside via the bypass of the venti-
lation unit.
Vitovent 200-C and Vitovent 300-F only:
With room cooling via the set heating/cooling cir-
cuit, the bypass is not activated for passive heating.
This prevents the heat drawn off via the heating/cool-
ing circuit being reintroduced from outside via the
ventilation unit bypass.
Note
Passive heating is not available for the other ventila-
tion units.
Additional conditions where passive heating or cooling
is not switched on: See chapter "Passive heating" and
"Passives cooling" in the "Function description".
254
!
300-F
300-W
X
!
300-F
300-W
X
300-F
300-W
X
X
X
Note
If "Economy mode" was previously active, the control
unit starts "Ventilation program".
Setting in min
Value
Meaning
"0"
Ventilation unit extract air temperature sensor
is used.
"1"
Room temperature sensor of the Vitotrol is
used.
!
Setting in the bit field (see chapter "Setting parame-
ters"): Several bits can be selected.
Note
opens the setting assistant.
Bit
Meaning
"Bit 1" Heating circuit A1/HC1
"Bit 2" Heating circuit M2/HC2
"Bit 3" Heating circuit M3/HC3
Note
The bypass may be enabled if no Bit is selected.
The setting value results from the combination of se-
lected bits.