Viessmann VITOTRONIC 200 Service Instructions Manual page 151

Heat pump control unit
Table of Contents

Advertisement

Refrigerant circuit
(cont.)
Message
Meaning
code
2F
Min. required evaporation
H
pressure undershot
30
Operating point outside
H
the compressor applica-
tion limits for longer than
max. time
36
Min. pressure differential
H
between high and low
pressure side exceeded
before compressor start
48
Suction gas superheating
too low
49
Evaporator max. operating
pressure (MOP) has been
reached; changeover from
superheating to pressure
control of the suction gas.
4A
Evaporation temperature
too low
80
Max. compressor current
H
exceeded
81
Max. compressor output
H
exceeded
82
Mains voltage too high
H
83
Mains voltage too low
H
84
Temperature at the inver-
H
ter too high
85
Temperature at inverter
H
too low due to low outside
temperature
86
H
Inverter power consump-
tion too high
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor does not start.
Compressor OFF
Compressor remains in op-
eration.
Compressor remains in op-
eration.
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Measure
Check low pressure sensor: See
message code "0A".
Check refrigerant charge. Adjust if
necessary.
Check the position of the operating
point: See "Compressor travel"
and/or "Compressor path".
If fault persists, notify a specialist.
Check high and low pressure sen-
sors: See message codes "05" and
"0A".
Check secondary circuit flow rate.
Check secondary pump.
Ensure pressure compensation be-
tween the high pressure and low
pressure sides. For this, switch the
4-way diverter valve with an "Actua-
tor test".
Check whether the correct coding
card is fitted. To check information,
see "System information".
In the event of recurrence: Have the
refrigerant circuit checked by a re-
frigeration engineer.
No action required
Check fan.
Check evaporator for ice formation.
Check evaporator temperature sen-
sor: See message code "09".
Test coil resistance at compressor. Re-
sistance on all windings must be simi-
lar (
10 %). For m
use a suitable
±
Ω
measuring device.
Test mains voltage at mains terminals:
If mains voltage is too high (+10 %),
clarify the cause in consultation with
the power supply utility.
Test mains voltage at mains terminals:
If mains voltage is too low (
clarify the cause in consultation with
the power supply utility.
Check fan at inverter heat sink. Re-
place inverter if necessary.
No action required
Test coil resistance at compressor. Re-
sistance on all windings must be simi-
lar (
10 %). For m
use a suitable
±
Ω
measuring device.
Diagnosis
10 %),
151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents