Viessmann VITOTRONIC 200 Service Instructions Manual page 295

Heat pump control unit
Table of Contents

Advertisement

Luster terminals, Vitocal 111-S/222-A/222-S
Terminals
Function
X3.8
Frost stat, cooling
X3.9
or
Jumper
X40.L1
Heat pump control unit power supply:
Phase L1
X40.
?
X40.N Neutral conductor terminal
Earth conductor terminal
PCBs and connection options
(cont.)
Explanation
Note
No parameters need to be set
No jumper should be installed if a power-OFF contact
is connected.
The compressor is "forced" off as soon as the contact
opens.
The power-OFF signal switches off the supply voltage
of the respective component (subject to the power
supply utility).
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
2
(3 x 1.5 mm
) and the cable for the power-OFF signal
can be combined in a single 5-core cable.
In connection with Smart Grid:
The power-OFF signal must not be connected.
Jumper must be installed.
Requires floating contact:
Closed: Safety chain has continuity
Open: Safety chain interrupted; heat pump shut down
Breaking capacity 230 V~, 0.15 A
Connected in series if 2 safety components are instal-
led
Insert jumper if no safety components are instal-
led.
Power supply 230 V~
295