6007 Hysteresis DHW temperature heat pump
The set value determines at what deviation from the
current set temperature ("Set DHW temperature
6000" or "Set DHW temperature 2 600C") DHW
heating with the heat pump starts.
A
B
F
D
E
Fig. 55
Set DHW cylinder temperature
A
Heat pump hysteresis ("Hysteresis DHW temper-
B
ature heat pump 6007")
Actual DHW temperature at the top cylinder tem-
C
perature sensor
Demand for DHW heating with heat pump
D
OFF
E
ON
F
6008 Hysteresis DHW temperature booster heater
The set value determines at what deviation from the
current set temperature ("Set DHW temperature
6000" or "Set DHW temperature 2 600C") DHW
reheating with the booster heaters starts.
C
t
E
!
Note
Set a lower value for "Hysteresis DHW temperature
heat pump 6007" than for "Hysteresis DHW temper-
ature booster heater 6008". Otherwise the proportion
of DHW heating provided by the electric heater will
increase.
≙
Setting 1
0.1 K
!
Fig. 56
Set DHW cylinder temperature
A
Heat pump hysteresis ("Hysteresis DHW temper-
B
ature heat pump 6007")
Booster heater hysteresis ("Hysteresis DHW tem-
C
perature booster heater 6008")
Actual DHW temperature at the top cylinder tem-
D
perature sensor
Demand for DHW heating with heat pump
E
Demand for DHW reheating with booster heater
F
OFF
G
H
ON
Parameter group DHW