Hysteresis Dhw Temperature Heat Pump - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

6007 Hysteresis DHW temperature heat pump

The set value determines at what deviation from the
current set temperature ("Set DHW temperature
6000" or "Set DHW temperature 2 600C") DHW
heating with the heat pump starts.
A
B
F
D
E
Fig. 55
Set DHW cylinder temperature
A
Heat pump hysteresis ("Hysteresis DHW temper-
B
ature heat pump 6007")
Actual DHW temperature at the top cylinder tem-
C
perature sensor
Demand for DHW heating with heat pump
D
OFF
E
ON
F
6008 Hysteresis DHW temperature booster heater
The set value determines at what deviation from the
current set temperature ("Set DHW temperature
6000" or "Set DHW temperature 2 600C") DHW
reheating with the booster heaters starts.
C
t
E
!
Note
Set a lower value for "Hysteresis DHW temperature
heat pump 6007" than for "Hysteresis DHW temper-
ature booster heater 6008". Otherwise the proportion
of DHW heating provided by the electric heater will
increase.
Setting 1
0.1 K
!
Fig. 56
Set DHW cylinder temperature
A
Heat pump hysteresis ("Hysteresis DHW temper-
B
ature heat pump 6007")
Booster heater hysteresis ("Hysteresis DHW tem-
C
perature booster heater 6008")
Actual DHW temperature at the top cylinder tem-
D
perature sensor
Demand for DHW heating with heat pump
E
Demand for DHW reheating with booster heater
F
OFF
G
H
ON
Parameter group DHW