Viessmann VITOTRONIC 200 Service Instructions Manual page 160

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
0E
Short circuit/lead break,
S
suction gas temperature
sensor (downstream of
evaporator)
10
Compressor has stopped.
H
13
Communication error
S
15
Inverter and compressor
S
incompatible
18
Compressor fault (general
S
message)
1E
EEV PCB faulty
S
1F
Parameter "Output com-
pressor stage 5030" not
set correctly
20
Condensing pressure too
H
high (control high pres-
sure)
21
Inadequate evaporation
H
pressure (low pressure
fault)
22
Excessively high hot gas
H
temperature
24
Compressor failed to start:
S
Message "88" has occur-
red 3 times successively.
26
Max. defrost time excee-
H
ded
33
Central heating/DHW
H
heating:
Secondary circuit flow
temperature too low
160
(cont.)
Heat pump characteris-
tics
Compressor OFF
Compressor OFF
Compressor OFF
Subject to other messages
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Compressor OFF
Defrost is terminated early.
Compressor remains in op-
eration, but does not re-
start.
Measure
Check resistance value (NTC 10 k
at connection J13 (T7) of the EEV
PCB: See "EEV PCB [4-3] / [4-4]".
No action required
Check the electrical connection be-
tween the refrigerant circuit controller
and the inverter.
Check whether the coding card match-
es the heat pump. To check informa-
tion, see "System information".
See further messages regarding the
compressor and inverter (message
code "80" and above).
Replace EEV PCB.
Set "Output compressor stage
5030" according to the type plate.
Then switch off the heat pump control
unit. Wait 1 min. Then restart the heat
pump control unit.
As for "D4 Control high pressure":
See "Message overview" for the heat
pump control unit.
As for "D3 Low pressure": See "Mes-
sage overview" for the heat pump con-
trol unit.
Have a specialist check the com-
pressor parameters ("5xxx").
Check whether the coding card
matches the heat pump. To check in-
formation, see "System information".
Check compressor drive.
Check inverter.
Check setting of "Evaporator tem-
perature for defrost end 5010".
Set to factory settings if necessary.
Check function of 4-way diverter
valve: See "Actuator test".
Check hydraulics in the secondary
circuit, e.g. whether all shut-off
valves are fully open.
Check secondary circuit flow rate.
Check flow and return temperature
in the secondary circuit.
Check flow and return temperature
sensor in the secondary circuit.
Check amount of refrigerant. Adjust
the amount of refrigerant if necessa-
ry.
Check temperature sensors in the
refrigerant circuit.
)
Ω

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents