Viessmann VITOTRONIC 200 Service Instructions Manual page 174

Heat pump control unit
Table of Contents

Advertisement

Diagnosis
Refrigerant circuit
Message
Meaning
code
3A
Safety high pressure
S
switch has responded.
4A
Evaporation temperature
too low
4B
EEV connecting cable
S
faulty
EEV stepper motor faul-
ty
56
Condenser frost risk
H
60
DHW heating via auxiliary
S
heat exchanger fault
61
Fan fault
S
62
Flow switch does not de-
S
tect a flow rate.
63
Lower outside tempera-
H
ture limit not reached
66
Motor overload relay or
S
safety equipment at the
soft starter has respon-
ded.
174
(cont.)
Heat pump characteris-
tics
Both compressors OFF
Compressors remain op-
erational.
Both compressors OFF
Both compressors OFF
Refrigerant circuit rever-
sal OFF
DHW heating is stopped.
Compressor runs on for
max. 5 min.
Both compressors OFF
Compressor off. The other
compressor may remain in
operation.
Measure
As for "C9 Refrigerant circ (SHD)":
See "Message overview" for the heat
pump control unit.
Check fan.
Check evaporator for ice formation.
Check evaporator temperature sen-
sor: See message code "09".
Check the EEV connecting cable.
Replace the connecting cable if nec-
essary.
Replace EEV.
Check hydraulics in the secondary
circuit, e.g. whether all shut-off
valves are fully open.
Check secondary circuit flow rate.
Check flow and return temperature
in the secondary circuit.
Check secondary circuit flow tem-
perature sensor in the appliance.
Check refrigerant charge. Adjust if
necessary.
Check temperature sensors in the
refrigerant circuit.
Check auxiliary heat exchanger flow
rate.
Check circulation pump for cylinder
heating.
Check cylinder loading pump.
Check if fan is blocked.
Carry out mechanical check of fan.
Check fan control or PWM signal at
the controller PCB: See "Controller
PCB and EEV PCB [6]".
Check secondary circuit flow rate.
Check secondary pump.
Test voltage at the controller PCB con-
nection: See "Controller PCB and EEV
PCB [6]".
0 V: Flow switch has responded.
230 V~: Flow switch has not respon-
ded.
No action required
Check soft starter. Check status in-
put at the controller PCB: See "Con-
troller PCB and EEV PCB [6]".
Check motor currents/motor over-
load relay.