D0A Flow Rate Reduced Ventilation - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Parameter group Ventilation
7D08 Set room temperature
Set extract air temperature for ventilation mode.
At extract air temperatures < "Set room tempera-
ture 7D08" minus 1 K, the bypass can be activated
for passive heating. The outdoor air/extract air is
not routed via the heat exchanger.
At extract air temperatures > "Set room tempera-
ture 7D08" plus 1 K, the bypass can be activated for
passive cooling. The outdoor air/extract air is not
routed via the heat exchanger.

7D0A Flow rate reduced ventilation

Vitovent
200-C
200-W
300-C
X
Set air flow rate for the "Reduced" operating status in
the ventilation time program (ventilation level
Setting subject to the building and engineering.
7D0B Flow rate nominal ventilation
Vitovent
200-C
200-W
300-C
X
Set air flow rate for the "Standard" operating status in
the ventilation time program (ventilation level
7D0C Flow rate intensive ventilation
Vitovent
200-C
200-W
300-C
X
Set air flow rate for the "Intensive" operating status in
the ventilation time program (ventilation level
Setting subject to the building and engineering.
7D0F Min. supply air temperature for bypass
Vitovent
200-C
200-W
300-C
X
252
(cont.)
!
300-F
300-W
X
).
2
!
300-F
300-W
X
).
3
!
300-F
300-W
X
).
4
300-F
300-W
X
Note
Further conditions must be met in order for passive
heating and passive cooling to be switched on: See
"Min. supply air temperature for bypass 7D0F" and
chapters "Passive heating", "Passive cooling" in the
"Function description".
Setting value 1
0.1 °C
Standard setting values:
Vitovent 300-F: Centrally between 85 m
"Flow rate nominal ventilation 7D0B"
Vitovent 200-C: Centrally between 70 m
"Flow rate nominal ventilation 7D0B"
or
Approx. 30 % lower than "Flow rate nominal venti-
lation 7D0B"
3
Setting in m
/h
Set the design flow rate from planning here.
3
Setting in m
/h
Standard setting values:
Vitovent 300-F: Centrally between "Flow rate nomi-
nal ventilation 7D0B" and 280 m
Vitovent 200-C: Centrally between "Flow rate nomi-
nal ventilation 7D0B" and 200 m
or
Approx. 30 % higher than "Flow rate nominal venti-
lation 7D0B"
Setting in m
3
/h
To prevent unwanted formation of condensate on the
supply air lines, the bypass for passive cooling is only
enabled under the following conditions:
3
/h and
3
/h and
3
/h
3
/h