E6 Fault At Lon Subscbr - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Troubleshooting
Message overview

E6 Fault at LON subscbr.

No communication via LON with the subscriber, e.g. a
lag heat pump of a heat pump cascade
Cause
Fault at LON subscriber
EE KM BUS subscriber
Cause
Communication with a KM BUS subscriber not possi-
ble.
EF Modbus subscriber
Cause
Communication with a Modbus subscriber not possible. Check Modbus1 and Modbus 2 subscriber lists ("Serv-
F2 Parameters 5030/5130
Energy statement not calculated correctly.
Cause
Compressor output not set.
FF New start
Information display, no restriction of functions: Indi-
cates that the heat pump has been re-started.
Cause
Heat pump control unit restart
If this occurs unexpectedly: Brief interruptions in the
power supply, e.g. loose contacts
Nothing displayed on programming unit display
1. Switch ON system ON/OFF switch.
2. Check heat pump control unit fuse; replace if nec-
essary.
3. Check whether there is power at the heat pump
control unit; switch on power supply if necessary.
4. Check the plug-in and threaded connections.
102
(cont.)
Measure
Read message memory at faulty LON subscriber. Rec-
tify fault at LON subscriber.
Measure
Check KM BUS subscriber list ("Service functions"
"KM-BUS subscriber").
Measure
ice functions"
"Modbus1 subscriber"/"Modbus2
subscriber").
Measure
Set "Output compressor stage 5030/5130" parame-
ter accordingly.
Measure
After restart: No action required
If this occurs unexpectedly:
Check power supply of heat pump control unit.
Check ribbon cable in heat pump control unit.
5. Replace programming unit if necessary.
6. Replace controller and sensor PCB if necessary.
Installation and service instructions of the rele-
vant heat pump.