Solving Of Technical Problems During Powering Up Of Ca62 - Teletek electronics CA62 Installation And Programming Manual

Alarm control panel
Table of Contents

Advertisement

In case of technical trouble  - No 220 V power supply, to solve the problem do as follows:
 Turn off the main power supply;
 Check the main power supply fuse F - 0.63А. If the fuse is blown out change it with new one. If the fuse is
not damaged, check the connection between the main power cables and the control panel.
 Switch on the main 220V power supply.
 Wait for 3 minutes and if after this period the alarm panel does not restores its normal operating call the
maintenance engineer.
In case of technical trouble  - Fuse burned, to solve the problem do as follows:
 Turn off the main power supply;
 Turn off the back-up power supply (open the CА62 mounting box and switch off the black wire to the
accumulator battery;
 Wait for 1 minute while the resettable (PTC) fuses F1, F2 and F3 are restored - see Figure 5.
 Switch on the main 220V power supply.
 Connect the black wire from the control panel to the accumulator battery.

Solving of Technical Problems During Powering up of CA62