In case of technical trouble - No 220 V power supply, to solve the problem do as follows:
Turn off the main power supply;
Check the main power supply fuse F - 0.63А. If the fuse is blown out change it with new one. If the fuse is
not damaged, check the connection between the main power cables and the control panel.
Switch on the main 220V power supply.
Wait for 3 minutes and if after this period the alarm panel does not restores its normal operating call the
maintenance engineer.
In case of technical trouble - Fuse burned, to solve the problem do as follows:
Turn off the main power supply;
Turn off the back-up power supply (open the CА62 mounting box and switch off the black wire to the
accumulator battery;
Wait for 1 minute while the resettable (PTC) fuses F1, F2 and F3 are restored - see Figure 5.
Switch on the main 220V power supply.
Connect the black wire from the control panel to the accumulator battery.
Solving of Technical Problems During Powering up of CA62
SUPPLeMeNtS - СА62 Alarm Control Panel