Installation and Programming Manual - СА62 Alarm Control Panel
At ADDReSSeS 40хх are assigned the attributes of the А and В partitions in the system. Every partition can be armed
and disarmed independently.
ADDRESS 4010 - PROGRAMMING OF EXIT TIME FOR PARTITION А
Exit time is assigned to Entry/Exit type zones attached to Partition A. A double-digit number between 1
exit time
and 99 seconds is entered. For an interval of time, less than 10 seconds, the first digit must be 0.
Partition А
The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the
digits can be browsed with the help of the arrows.
Default settings - 45 sec.
ADDRESS 4011 - PROGRAMMING OF ENTRY TIME FOR PARTITION А
Entry time is assigned to Entry/Exit type zones attached to Partition A. A double-digit figure between 1
entry time
and 99 seconds is entered. For a time interval of less than 10 seconds, the first digit must be 0.
Partition А
The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the
digits can be browsed with the help of the arrows.
Default settings - 15 sec.
ADDRESS 4012 - PROGRAMMING OF BELL TIME FOR PARTITION А
Duration is set for the bell time of the sirens attached to Partition A. A double-digit number between 0
Bell time
and 99 minutes is entered. For a time interval of less than 10 seconds, the first digit must be 0.
Partition А
The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the
digits can be browsed with the help of the arrows.
Default settings - 03 min.
ADDRESS 4013 - PROGRAMMING OF BELL DELAY FOR PARTITION А
Delay is set for initiating the bell time of the sirens attached to Partition A. A double-digit number be-
tween 0 and 99 seconds is entered. For a time interval of less than 10 seconds, the first digit must be
Bell Delay
0.
Partition А
The indication is hexadecimal and the digits are displayed one by one. To view the introduced data, the
digits can be browsed with the help of the arrows.
Default settings - 0 min.
ADDRESS 4014 - PROGRAMMING OF AUTO-ARM TIME FOR PARTITION А
A time (HH:MM) for automatic arming at Partition A in the system is set.
Auto-ARM
time
Note: To take effect the programmed time on this address it is necessary the attribute "3. Auto Arm
Partition А
Enbl." at ADDRESS 4016 to be assigned.
ADDRESS 4015 - FIRE SIGNAL DURATION FOR PARTITION А
The duration of the alarm signal for a FIRE event at Partition A is assigned at this address.
FIRe Signal
Programming this address affects the performance of the programmable SIREN output.
Duration
Every click of a digital button alternatively changes the type of duration of the sound signal. The display
Partition А
indication is shown in the tables.
Until a valid
There is a FIRE alarm signal until a valid system
user code is
user or master user code is introduced.
entered
Until the Bell
time at
The FIRE signal duration is set at address 4012
Address
BELL TIME.
4012 ends.
Default settings - Until a valid user code is entered

4. PARtItIoNS PRoGRAMMING

Indication
LeD
     
Indication
LeD
(1) (2) (3) (4) (5) (6)
     
LCD
1 2 3 4 5 6
LCD