Installation and Programming Manual - СА62 Alarm Control Panel
All keyboard models are factory equipped with 4 terminals for connecting to СА62 control panel and two other terminals
for connecting to ZONE 1. Note: At LED61 keyboard, the input for ZONE 1 is equipped with two 10-cm long wires - black
and white for the bus connection. These terminals are marked with the respective colors.
The colors must be observed when connecting the keyboards to the СА62 Control Panel (see Figure 9). Note:
The connection in the connection below is principled. Note that in some keyboards the terminals for connecting to
ZONE 1 could be situated above the terminals for connecting to the control panel.
The zone cables are white and black in color. The zone in the keyboards HAS Not to be balanced (except LeD62
and LeD63VG Se keyboards - the keyboard zone can be balanced with setting the ZoNe eoL jumper, see the
jumpers explanation on Figure 10b). the zone in all model keyboards HAS Not to be programmed as double
zone also. When more than one keyboard are connected to the control panel, each keyboard have to be assigned with
individual zone number - 1 or 7. Activating any keyboard zone shall be regard as an activation of ZONE 1 or ZONE 7,
according the individual programming.
No more than 4 keyboards (irrespective of their type) can be connected to one control panel. Each keyboard must be
assigned an individual address, by placing the jumper on the keyboard at its respective place (see Figure 10а). The
individual address ensures TAMPER event identification, whenever the TAMPER switch of the respective keyboard is
turned on.
The individual address of each keyboard is assigned with the help of a jumpers. Following the table (see Figure 10а)
the respective address could be programmed. The individual address of each keyboard in the system can be checked
at ADDRESS 7000 from the Engineer menu (see page 47).
The JT jumper must be placed where only one keyboard has been connected. Where more than one keyboards are
connected, the Jt jumper should be placed on the most distant one. the Jt jumper is set by default.
The cable connecting the LED61 Keyboards to the CA62 Control Panel must be no longer than 250m and have a cross-
section of no less than 0.25mm.
Address
1
Jumper
J0
J1
J2
1)
2)
Figure 10b. Jumper location and zone balancing of LED62 and LED63VG SE keyboards.
The parameters and the functions of the buttons for each keyboard can be programmed at ADDRESSES 70xx, accord-
ing to the set with jumper address of the keyboard.
Keyboard:
(Se)
LCD64
Figure 9. Connecting keyboards to CA62 control panel.
Legend:
2
3
4
NOTE: The JT jumper must be set in the most far unit in the bus.
Figure 10a. Table for keyboard address programming.
the LeD keyboard zone is not balanced.
The jumper Zone EOL is removed.
The zone has two states:
• zone closed (the switch is closed)
• zone open (the switch is open)
the LeD keyboard zone is balanced.
The jumper Zone EOL is set.
The zone has three states:
• zone closed (the switch is closed) - item 1
• zone open (the switch is open) - item 1
3)
• tamper - items 2 and 3
ZONE 1
DETECTORS WIRES
- The jumper is removed;
- The jumper is set
CA62 control
panel terminals
Jumper location for
keyboard models:
LED61, LCD62,
LCD62B, LCD63,
LCD63SE, LCD64
Jumper location
for keyboard
models:
LED62
LED63VG SE
NOTE: The JT jumper
must be set in the most
far unit in the bus.