Installation and Programming Manual - СА62 Alarm Control Panel
The output is activated, when there is an alarm event in the system.
For all kinds alarm events the siren will activate for programmed bell time for the respective partition
(at ADDReSS 4012 for Partition А and ADDReSS 4022 for Partition В) or until a valid user code is
entered.
3. SIReN
In case of alarm event in FIRE type zone, the siren is activated in sequence of impulses (1 second on,
1 second off) until a valid user code is entered. With Fire Duration bell time set at ADDReSSeS 4015
and 4025, the "SIREN" output will be restored when the bell time is over or after a valid user code is
entered.
4. teCH.
It is activated in case of occurring "Low BATT", "Tel line fault" or "Blown fuse" events and does not
tRBL
depend on the Pulse / Latch parameter.
The output way of activation (restoring) is assigned at this address.
5. PULSe /
In SUPPLEMENT D are shown detailed algorithms for Key-Switch type
LAtCH
zone operation.
6. PoLARItY The active level for activation of the output is assigned at this address.
-
Default settings
POLARITY /+12V/
ADDReSS 3012 - PGM1 AttACHMeNt
PGM 1
At this address the PGM 1 attachment to any of the two partitions in the system is assigned. The output
Attachment
can be attached to the both partitions in the system at the same time.
Partition А
1. PARt A
The PGM is attached to Partition A. (It is activated in
case of event in the Partition A.)
Partition В
2. PARt B
The PGM is attached to Partition B. (It is activated in
case of event in the Partition B.)
-
Default settings
PART A
ADDReSS 3013 - PGM 1 eXteNSIoNS
At this address the PGM1 EXTENSIONS parameters are assigned. The output can be activated in
PGM 1
case of 20 additional events occurring. The engineer have to enter one two digit number of the addi-
extensions
tional parameter - from 00 to 19. The description of the parameters is given in the table below.
00. No ex-
No additional parameter for PGM 1 output is assigned.
tension
The output is activated in case of lowering the accumulator voltage under 11.4V, damaged battery fuse
01.
(BATT) or missing battery.
Battery
The output is restored after the charging level of the battery reaches value of 11.8V. The restoration of
trouble
the output does not depend on the Pulse / Latch parameter.
02.
The output is activated in case of blown out fuse (activated PTC fuse). This programming does not
Blown
depend on the Pulse / Latch parameter.
Fuse
The output is activated in case of trouble or missing of the telephone line
The possible activating events are:
03.
• telephone line is missing
telephone
• "Dialing tone" is missing
Line
• no communication with Monitoring station 1
trouble
• no communication with Monitoring station 2
This parameter does not depend of programmed Pulse/ Latch parameter. The output always follows
the event.
LeD
     
LeD
     
ADDReSS 3013 description continues on page 37
Indication
Attribute
LeD
LCD
Pulse
5
Latch
(5)
Indication
Active
level
LeD
LCD
0V
6
+12V
(6)
Indication
LCD
(1) 2 3 4 5 6
Indication
LCD
1 (2) 3 4 5 6