Installation and Programming Manual - СА62 Alarm Control Panel
ADDReSS 2014 - ZoNe 1 AttRIBUteS AUX
At this address are assigned only parameters "ATTRIBUTES AUX" for Auxiliary type zone.
Only one attribute AUX can be assigned at this address - a number from 00 to 11.
With an assigned AUX attribute and alarm in the zone, a system status message will the generated in
Zone 1
the memory LOG file, which can be programmed to PGM output. The PGMx outputs programming is
Attributes
described in item 3. PGM and SIREN Outputs Programming in SECTION Programming.
AUX
The indication is in hexadecimal numbers - see the Table in SUPPLEMENT С.
the parameters "AttRIBUteS AUX" are as follows:
24h Burglary - 24-hour burglary alarm zone
With this attribute assigned the zone will be active irrespective of the arming type. The zone will oper-
00
ate as INSTANT type and the programmable ALARM and SIREN outputs, and the system communica-
tor will be activated.
01
Battery Low - Low battery charging level.
02
Gas Detector - Activated gas detector.
03
Water Leakage - Activated flood detector.
04
AC Loss - Main power supply lost.
05
GSM Link trouble - GSM communication failure.
06
Refrigeration - Activated refrigeration detector.
07
Loss of Heat - Loss of heat in the premises.
08
Foil Break - Detector foil break.
09
Low Bottled Gas Level - Activated low bottled gas detector.
10
High temperature - High temperature in the premises.
11
Low temperature - Low temperature in the premises.
-
Default settings
00. 24h Burglary attribute
ADDReSS 2015 - ZoNe 1 AttACHMeNt
At this address the ZONE 1 attachment to any of the two partitions in the system is assigned. To ac-
tivate the parameter press the digit button with the respective partition number. Next pressing of the
same digit button will deactivate the parameter.
Note: The ZONE can be attached and to the both partitions in the system. In this case the E/E, Fol-
Zone 1
low and Instant type zones will be armed only if the both partitions in the system are armed. Besides,
Attachment
in case of alarm in a zone attached to the both partitions, records for the both of the partitions will be
present in the system memory LOG file.
Attention: If the ZONE is not attached to any of the both partitions in the system, the control panel will
not check and signalling for its state and status.
Partition А
1. PARt A
The ZONE is attached to Partition A.
Partition B
2. PARt B
The ZONE is attached to Partition B.
-
Default settings
PART A
ADDReSSeS 2020 ... 2025 - ZoNe 2 PRoGRAMMING
The programming is the same as that at ADDReSS 2010 - 2015, as the type, attributes (parameters 1, 2 and 3, AUX)
as the attachment of ZONE 2 are assigned.
The doubling zone type connection can be realized to ZONE 2 - see the Figure 6 c. The ZONE 2 corresponds to ZONE
8. The type of connection can be programmed at ADDRESS 2026 with setting the "4.Doubling" attribute.
Default settings - type Unused; ATTRIBUTES 1 - AUTOBYPASS and BYPASS; ATTRIBUTES 3 - Disarm Enable;
ATTRIBUTES AUX - 00. 24 h Burglary; Attachment - PART А