The zone parameters in the system are programmed at ADDReSSeS 2xxx. The parameters for every zone are pro-
grammed separately, as every zone has to be attached to one or the both partitions in the system.
ADDReSS 2000 - NUMBeR oF ACtIVAtIoNS PeR ZoNe FoR AUto BYPASS MoDe
The number of activations (number of alarm cycles from 0 to 9) in one arm mode, which have to be
AutoBypass
accomplished for a zone with an assigned AUTO/BPS parameter, are entered at this address. After
Counter
reaching the indicated number of activations, the respective zone will be automatically bypassed.
When disarmed and then again armed the respective zone will remain armed.
Default settings - 6
ADDReSS 2001 - eNABLING FoR INStANt tYPe ZoNeS
Intrusion in any Instant type zone during exit time is enabled or disabled at this address. Enabling this
enable
operating mode would reduce the probability for a false alarm signal to be triggered off by mistake on
Instant
behalf of the user.
The parameter status can be changed with pressing of random button of the keyboard.
Disabled intrusion in INSTANT type zones during exit
No
type.
Enables intrusion in INSTANT type zones during exit
YeS
type.
-
Default settings
NO
ADDReSS 2010 - ZoNe 1 tYPe
The zone type is set at this address. only one type can be selected for a given zone. Press the
digital button, which corresponds to the number of the desired type. At LED keyboards the indication
is hexadecimal and is shown in the table in SUPPLEMENT С.
At LCD keyboards the information for the zone type is visualized on the display in two ways - with
hexadecimal number and as a natural number on the place of the last digit of the clock.
Example for programming of the Zone 1 as 1. Entry/Exit type using LCD62 keyboard:
ZoNe 1
type
the Zone types are as follows:
0. Unused
The zone is not being used.
entry- exit zone.
Provides time to arm and disarm the site. After arming, the detector, which
was triggered off in this zone, will not sound an alarm until the programmed
EXIT TIME expires.
1. entry/exit
No violation of the zone when in armed mode will sound an alarm before the
programmed ENTRY TIME expires.
A sound signal is activated from the keyboard buzzer during entry and exit
time.

PRoGRAMMING oF ZoNeS

2.
ADDReSS 2010 description continues on page 29
Indication
LeD
     
Indication
LeD
(1) (2) (3) (4) (5) (6)
     
     
     
1 2 3 4 5 (6)
LCD
1 2 3 4 5 6
LCD
Indication
LeD
LCD
1 2 3 4 5 6
Indication
LeD
LCD