Installation and Programming Manual - СА62 Alarm Control Panel

2.12 Installing of AJAX LAN Module in CA62 Alarm Control Panel

AJAX Module is an additional accessory for built-in installation in CA62 or any other security or fire control system. It
transmits the system status to Monitoring centre or to the User via Internet. The AJAX module enables easy monitoring
and transmitting of alarm events occurring in the security system to existing Monitoring centre using standard monitor-
ing software.
For more information please refer to the distributor of this equipment.

2.13 Connecting of UWE432 Universal Wireless Expander to CA62 Alarm Control Panel

UWE432 is a universal device for expanding existing wired alarm security systems. UWE432 communicates by means
of two-way radio connection with the AVA series wireless devices. The UWE432 supports up to 32 AVA series wireless
devices. Attention: the panel should be programmed to operate in double zone connection mode (at addresses
20х6, х - from 2 to 7, "4. Doubling" parameter is set). It is obligatory to set a jumper on connector MODE at
UWe432 main board!
Figure 18. Connecting UWE432 universal expander to CA62 alarm control panel.
For the installation of AJAX LAN module in the CA62 universal plastic box
refer to sequence shown in Figure 16 as follow the steps:
- Break off the pins from the plastic box.
- Fix the mounting holes to the respective pins and carefully push down.
- Fix the module to the plastic box with the screw from the spare parts kit.
Figure 16. Installing of AJAX LAN Module.
AtteNtIoN: the connecting between AJAX LAN module and
CA62 alarm control panel MUSt Be done only with power
supply oFF and set ReSet jumper on the AJAX module!
For the connection between AJAX LAN mod-
ule and CA62 alarm control panel refer to
Figure 17, as follow the steps:
- With Power supply oFF, connect the
AJAX module to the CA62 by means the
interface cable (Note: the interface cable is
not included in the spare parts kit for CA62.)
- Connect LAN cable for Internet connec-
tion.
- Place a reset jumper.
- Turn the Power supply ON and wait
for 5 seconds in order to configure and to
obtain the default factory parameters.
- Remove the RESET jumper.
Figure 17. Connecting of AJAX LAN
module to CA62.