ADDReSS 2026 - tYPe oF BALANCING FoR ZoNe 2
The type of ZONE 2 balancing is selected at this address. Every consecutive pressing of a digital but-
ton alternatively changes the type of balancing. Display indications are given in the tables below.
type of
The doubling zone type connection can be realized to ZONE 2 - see the Figure 6 c.
balancing for
ZoNe 2
Note: When connecting one fire detector to the zone do not assign any type of balancing for it. When
connecting 2 fire detectors to the zone you have to assign the 4.Doubling attribute!
Connecting of balancing resistor.
1. eoL
With or without TAMPER in the circuit.
2. Fast/
Programmable sensitivity of the zone between 10
Regular
and 250ms.
The zone will be bypassed for a 120 second pe-
3. Power-up
riod after power-up of the system (that eliminated
delay
the false alarms in the initial power-up of the control
panel).
Doubling zone connection. The parameter is as-
signed when the doubling zones connection is real-
ized in the system. Activating this parameter will dis-
4. Doubling
able the setting of 1.EOL attribute at the beginning
of this address, as considers that the connecting of
balancing resistors in this case is with tamper in the
circuit.
-
Default settings
no attribute is set
ADDReSS 2030 ... 2036 - ZoNe 3 PRoGRAMMING
The programming is the same as that at ADDReSS 2010 - 2015, as the type, attributes (parameters 1, 2 and 3, AUX)
as the attachment of ZONE 3 are assigned.
The doubling zone type connection can be realized to ZONE 3 - see the Figure 6 c. The ZONE 3 corresponds to ZONE
9. The type of connection can be programmed at ADDRESS 2036 with setting the "4.Doubling" attribute.
Default settings - type Unused; ATTRIBUTES 1 - AUTOBYPASS and BYPASS; ATTRIBUTES 3 - Disarm Enable;
ATTRIBUTES AUX - 00. 24 h Burglary; Attachment - PART А
ADDReSS 2040 ... 2046 - ZoNe 4 PRoGRAMMING
The programming is the same as that at ADDReSS 2010 - 2015, as the type, attributes (parameters 1, 2 and 3, AUX)
as the attachment of ZONE 4 are assigned.
The doubling zone type connection can be realized to ZONE 4 - see the Figure 6 c. The ZONE 4 corresponds to ZONE
10. The type of connection can be programmed at ADDRESS 2046 with setting the "4.Doubling" attribute.
Default settings - type Unused; ATTRIBUTES 1 - AUTOBYPASS and BYPASS; ATTRIBUTES 3 - Disarm Enable;
ATTRIBUTES AUX - 00. 24 h Burglary; Attachment - PART А
ADDReSS 2047 - NUMBeR oF ACtIVAtIoNS IN ZoNe 4 IN PULSe CoUNt MoDe
The number of pulses for zone 4 in Pulse Count mode are entered at this address.
The indication is in hexadecimal numbers, as for LCD keyboards the entered value is also visible at the
Zone 4
last clock digit. The value for the pulse counter can be entered while the digit is blinking.
Pulse coun-
Values of between 0 and 9 pulses can be entered here. The 0 value blocks the Pulse Count mode and
ter
the zone can then function with the regular time for detecting activation.
The working algorithm for zone 4 in Pulse Count mode has been clarified in
Item 2.6.
Default settings - 0
Installation and Programming Manual - СА62 Alarm Control Panel
eoL Connecting
Without TAMPER
With TAMPER
Sensitivity
Regular (250ms)
Fast (10ms)
Power-up delay
Without zone bypass
Zone bypass (120 sec)
Mode
Single zone
Doubling zone
33
Indication
LeD
LCD
1
(1)
Indication
LeD
LCD
2
(2)
Indication
LeD
LCD
3
(3)
Indication
LeD
LCD
4
(4)

Advertisement

Table of Contents
loading

Table of Contents