ADDReSS 6011 - eNteRING PRotoCoL 1 NUMBeR FoR tHe CoMMUNICAtoR
Enter central station No. 1 protocol number from the attached table. Valid are the symbols from 1 to
2, where:
Button
PRotoCoL 1
1
2
*
Note: See also the code tables in the APPENDIX C.
Default settings - SIA
ADDReSS 6012 - tYPeS oF MeSSAGeS tRANSMItteD FRoM tHe DIGItAL CoMMUNICAtoR FoR PRot. 1
At this address are assigned the type of the messages which will be transmitted to a central monitoring
station in case of alarm condition through telephone number 1. Here also is assigned and the transmit-
ting algorithm of the messages. The following report options can be set:
1. Message report from at least one of the two telephone numbers - Alternative report.
2. Independent message report to both telephone numbers - Split report.
3. Message report from one telephone number, which is also duplicated at the second - Both report.
Note: To the telephone number 1 can be programmed to be transmitted only chosen messages. In
case the user wants some messages to be transmitted and through telephone number 2, then the
same chosen messages have to be assigned and at ADDRESS 6022. If it does not matter through
Message
which of the both telephone numbers, 1 and/or 2, the messages are sent, you have to leave the AD-
type
DRESS 6022 with its default programming (No messages are assigned).
The digital buttons 1 to 6 are used for programming. Pressing them each time will alternatively change
the status of the respective message type - report (active status of the parameter) or no report (inactive
status of the parameter). At the end of the procedure only those parameters, which correspond to the
designated for report messages, should remain activated on the display.
1. ALARM
ALARM and TAMPER type messages are transmitted.
2. PANIC
PANIC type messages or entered ambush code are transmitted.
3. FIRe
FIRE and TAMPER type messages are transmitted.
4.oN/
BYPASS, ON/OFF type messages and engineer programming input are transmitted.
oFF+BPS
5. MeDICAL MEDICAL type messages are transmitted.
6. tRoUBLe TROUBLE and TEST type messages are transmitted.
Default settings - ALARM, PANIC, FIRE, ON/OFF+BPS, MEDICAL and TROUBLE
ADDReSS 6020 - eNteRING teLePHoNe NUMBeR 2 FoR tHe CoMMUNICAtoR
A telephone number is assigned for communicating with central station - No. 2.
The indication is hexadecimal. The telephone number must not exceed 16 characters.
Some special functions can be entered by using the next button combinations:
1. Buttons ARM + 0 - Switches on "pulse dialer".
2. Buttons ARM + 1 - Switches on "tone dialer".
telephone
3. Buttons ARM + 2 - 2 seconds pause.
number 2
4. Buttons ARM + 3 - Switches on "Wait dial tone".
for the com-
5. Buttons ARM + 4 - "Blind dialing"; Switches off "Wait dial tone".
municator
6. Buttons ARM + 5 - Deletes the entered telephone number*.
Dialing has been assigned a default tone signal and "Wait dial tone" function is switched on.
The entered telephone number and the special functions can be saved with pressing the ENT button.
* Note: When there are no entered phone numbers at this address, use this key combination to disable
the option "listening to the telephone line".
Default settings - there are no configured numbers, tone dialer
Installation and Programming Manual - СА62 Alarm Control Panel
Protocol
ADEMCO CONTACT ID*
SIA*
At the default settings the display will show:
LeD
     
Indication
LeD
     
     
LCD
(1) (2) (3) (4) (5) (6)
LCD
1 2 3 4 5 (6)
1 2 3 4 (5) 6
43