Installation and Programming Manual - СА62 Alarm Control Panel
• LED blinks / ( ) at LCD - expecting confirmation from central station
5: Wait
"kiss-off"
• active state /
• active state /
6: All sent
fully transmitted to the central station
ADDReSS 0024 - DISPLAY LoG eVeNtS
The events recorded in the power independent memory of the station can be traced with the help of
the arrows. The first event which is visualized is the last recorded.
Viewing the LOG with a LED keyboard
The indication has a hexadecimal expression - see SUPPLEMENT С.
Display
Viewing the LOG with a LCD keyboard
LoG
Use the 1, 2 and 3 buttons to view, as follows:
- Button 1 - Displays information for the event time;
- Button 2 - Displays information for the event time;
- Button 3 - Displays information for the LOG code. See SUPPLEMENT C for detailed description of
Coding recordings in log events.
ADDReSS 0025 - DISPLAY UDL PRoCeSS
The Up / Down Load process can be directly monitored at this address.
A single click on the 0 button aborts current communication.
A single click on the AND button can start manual communication. This will ignore the counter for in-
UDL/
coming calls and will directly proceed on to step 2.
Direct UDL
The meaning of the symbols is given below, as the "active state" means permanent lighting of the
LEDs (LED keyboard) or enclosed in brackets number (LCD keyboard).
The CLEAR button exits ADDReSS 0025.
• LED blinks / ( ) at LCD - each blink indicates one received call
1: Ring
• active state / or (1)/ - the number of designated at ADDReSS 6904 calls have been received
• LED blinks / ( ) at LCD - a CALL BACK process
2: Call back
• active state / or (2)/ - CALL BACK completed
• LED blinks / ( ) at LCD - process of detecting a carrier
3: Currier
• active state / or (3)/ - established connection to PC
• LED blinks / ( ) at LCD - receiving data from central station
4: Receive
• active state / or (4)/ - data pack received
• LED blinks / ( ) at LCD - transmitting data to central station
5: transmit
• active state / or (5)/ - data pack transmitted
6: end
• active state / or (6)/ - up / down loading completed
ADDReSS 0026 - DIGItAL CoMMUNICAtoR HARDWARe teSt
A step by step test of the hardware of the digital communicator can be done at this address. A light-
emitting diode on the keypad lights up to visualize every step. There is no time limitation for the
steps.
Comm. HW
!During the test the digital communicator is blocked and disabled!
test
The first step of the digital communicator hardware test automatically begins after ADDReSS 0026 is
entered. Transition between the various steps can be accomplished with the respective digital buttons
1 to 5 or with the help of the arrows. The light-emitting diodes or enclosed in brackets number, indicate
the number of the current step:
The built-in relay is activated at this step. As a result the telephone line, connected to terminals A and
B, is discontinued from terminals A1 and B1, where the local telephone device or some other appara-
1: Relay
tus using the telephone line, should be connected. During this step the telephone line voltage should
be measured at terminals A and B (to read usually between 40 and 60 V DC) and at terminals A1 and
B1 (to read 0 V DC).
or (5)/ - transmitted data has been successfully received
or (6)/ - communication process has been completed and all data has been success-