CANopen option board OPTE6 - technical data
vacon • 31
4.2.1
Isolated ground connection
The OPTE6 option board is galvanically isolated. In CANopen networks that are completely galvan-
ically isolated the CAN ground signal is carried in the cable line. It is connected at only one point
into common ground potential. If one CAN device with not galvanically isolated interface is connect-
ed to the network, the potential for isolated CAN ground is given. Therefore only one device with not
galvanically isolated interface may be connected to the network.
E6 Option Board
E6 Option Board
E6 Option Board
9384.emf
Figure 3. Completely isolated nodes
E6 Option Board
E6 Option Board
Non isolated node
9385.emf
Figure 4. CAN network with one non-isolated node