Emcy Object - Vacon OPTE6 User Manual

Canopen option board
Hide thumbs Also See for OPTE6:
Table of Contents

Advertisement

CANopen protocol description
Table 10: Node guarding RTR frame (remote request)
CAN ID
LENGTH
0x700 +
0x0
Node ID
Table 11: Node guarding response
CAN ID
LENGTH
0x700 +
0x1
Node ID
3.3.3

EMCY object

Option board works as an EMCY producer. The EMCY object is transmitted when a fault occurs in
the drive or option board. To switch off the EMCY producer, disable the EMCY COB-id by writing MSB
bit to 1 (object 0x1014).
When an error occurs, the EMCY message is transmitted with the current value of the error
register and the error code is inserted into the pre-defined error field list. The newest error code is
always the first sub-index on the error field list. When all active errors are cleared, an empty EMCY
object is transmitted.
If a drive-internal fault occurs, the MSEF field contains the drive fault code. See the application and
user manual for possible fault codes. The ER field holds a bit coded value of the error type. See
object 0x1001 for more details.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
RTR
DATA0
DATA1
1
DATA0
DATA1
t
Status
Table 12: Node guarding slave status
Status
Value
Description
0x4
Stopped
0x5
Operational
0x7F
Pre-operational
Table 13: Node guarding related objects in OD
Index
Description
0x100C
Guard time
0x100D
Life time factor
DATA2
DATA3
DATA4
DATA2
DATA3
DATA4
vacon • 11
DATA5
DATA6
DATA7
DATA5
DATA6
DATA7
3