CANopen protocol description
Configuration of the transmit PDO parameter, when the bypass parameter set is restored, is the
following:
Table 60: Transmit PDO 1 communication parameter record
Index
Sub-index
0
1
2
0x1800
3
4
5
6
Table 61: Transmit PDO 2 communication parameter record
Index
Sub-index
0
1
2
0x1801
3
4
5
6
Table 62: Transmit PDO 3 communication parameter record
Index
Sub-index
0
1
2
0x1802
3
4
5
6
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Value
Name
6
Highest sub-index
0x00000180+id
COB-ID
0xFE
Transmission type
0x03E8
Inhibit time
-
Reserved
0x0
Event timer
0x0
Sync start value
Value
Name
6
Highest sub-index
0x00000280+id
COB-ID
0xFE
Transmission type
0x03E8
Inhibit time
-
Reserved
0x0
Event timer
0x0
Sync start value
Value
Name
5
Highest sub-index
0x00000400+id
COB-ID
0xFE
Transmission type
0x03E8
Inhibit time
-
Reserved
0x0
Event timer
Sync start value
vacon • 29
Data type
Access
UNSIGNED8
ro
UNSIGNED32
r/w
UNSIGNED8
r/w
UNSIGNED16
r/w
UNSIGNED8
ro
UNSIGNED16
r/w
UNSIGNED8
w
Data type
Access
UNSIGNED8
ro
UNSIGNED32
r/w
UNSIGNED8
r/w
UNSIGNED16
r/w
UNSIGNED8
ro
UNSIGNED16
r/w
UNSIGNED8
w
Data type
Access
UNSIGNED8
ro
UNSIGNED32
r/w
UNSIGNED8
r/w
UNSIGNED16
r/w
UNSIGNED8
ro
UNSIGNED16
r/w
UNSIGNED8
w
3