CANopen protocol description
All communication errors are reset if a reset command is given. This does not however reset drive
faults if there are active error sources.
EMCYs are also created in some cases, even though a fault is not created. These are for notification
only.
3.4
SDO protocol
The Option board contains one SDO server. The SDO protocol provides a direct access to the object
entries of the object dictionary of the CANopen device. Each message is acknowledged by the
server. The protocol is mostly used to set and read parameters from the object dictionary at the
pre-operational state. Some objects have limitations for SDO usage at the operational state.
Up to four bytes can be transferred by using the expedited transfer, where the data fits into one CAN
message. For bigger than 4-byte object sizes, segmented transfer must be used. Optionally, block
transfer is also possible with bigger data types. Block transfer is most efficient with big data sizes.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Table 18: Notification EMCY objects
EEC
Description
0x8110
CAN overrun (objects lost)
0x8210
PDO not processed due to length error
0x8220
PDO length exceeded
0x8240
Unexpected SYNC data length
Table 19: EMCY-relate objects in OD
Index
Description
0x1001
Error register
Pre-defined error field
0x1003
list
0x1014
EMCY object COB-ID
Table 20: SDO-related objects in OD
Index
Description
SDO server parameter
0x1200
object
vacon • 13
3