160
MODBUS Ref.
10030
10031
10032
10033
10034
10035
10036
10037
10038
4xxxxx Registers – Bypass
MODBUS addressing of 4xxxxx registers maps the drive's parameters and other
values when using the drive device ID. The bypass's parameters and other values
are mapped when using the bypass device ID.
Registers 400001 ... 400099 - Bypass
The bypass maps its parameters and other data to the 4xxxxx holding registers as
follows:
400001...400099 map to bypass control and actual values. These registers are
descibed in the table below.
400267...465535 map to bypass parameters 0101...255255. Register addresses
that do not correspond to bypass parameters are invalid. If there is an attempt to
read or write outside the parameters addresses, the Modbus interface returns an
exception code to the controller.
Register addressing is done as follows: Use 400000 + 256 * (parameter group) +
parameter index.
For example: bypass parameter 0111 would be mapped to 400000 + 256 *
1 = 400267.
The following table summarizes the 4xxxxx bypass control registers
400001...400099:
MODBUS Ref.
400001
400004
Note: All parameters referenced are bypass parameters.
Embedded fieldbus
ACH580 E-Clipse bypass and packaged drive user manual
1.1.1 MODBUS Registers (1xxxx)
Bypass Device ID
Bit
29
30
31
Bypass DI1
Bypass DI2
Bypass DI3
Bypass DI4
Bypass DI5
Bypass DI6
MODBUS Registers (40001 to 40099)
Internal location
(All profiles)
Control Word
Status Word
BCU PROFILE
Bypass Device ID
Maps directly to BCU profile
control word.
Maps directly to BCU profile
status word.