ACH580 E-Clipse bypass and packaged drive user manual
Code
1631
1640
1641
1642
1643
1644
Group 17: Override 2
Code
1701
1702
1703
1704
1706
1707
1708
Name
Resolution
DRV/BYPASS
1
PASS SET
PASS CNFRM
ABB ACCESS
FB LOCK
DNLD LOCK
Name
Resolution
OVERRIDE 2
1
PERMSV OVR
1
INTLK1 OVR
1
INTLK2 OVR
1
INTLK4 OVR
1
FAULTS OVR
1
OVRD2 MODE
1
Group 16: System Control
Range
Default
0 = KEYPAD
KEYPAD
1 = DI5
(0)
0 – 65535
0
0 – 65535
0
0 = LOCKED
LOCKED
1 = OPEN
(0)
0 = LOCKED
OPEN
1 = OPEN
(1)
0 = LOCKED
OPEN
1 = OPEN
(1)
Group 17: Override 2
Range
0 = NOT SEL
1 = DI5
2 = COMM
0 = ACKNOWLEDGE
DISREGARD
1 = DISREGARD
0 = ACKNOWLEDGE
DISREGARD
1 = DISREGARD
0 = ACKNOWLEDGE
DISREGARD
1 = DISREGARD
0 = ACKNOWLEDGE
DISREGARD
1 = DISREGARD
0 = ACKNOWLEDGE
DISREGARD
1 = DISREGARD
1 = BYPASS
2 = VFD
3 = VFD/BYPASS
4 = STOP
Description
Selects source for drive/bypass
mode command.
(0) Keypad – The drive/bypass
mode selection is made
from the bypass keypad
(DRIVE or BYPASS select
keys).
(1) DI5 – The drive/bypass
mode selection from the
bypass keypad is disabled
and selection is made from
the digital input. When DI5
is energized the system is
set to bypass mode.
Sets the passcode that is
compared against parameter
1618- PASS CODE. Passcode
required to open.
Confirms the setting of
parameter 1640 - PASS SET.
Locks access to factory only
parameters and factory debug
tool. Passcode required to open.
Allows Fieldbus writing of
parameters. Applies to
embedded and FBA.
Does not affect control of the
bypass over the fieldbus.
Does not affect bypass
parameters in group 53- FBA
DATA OUT.
Does not affect writing of
parameters to the drive.
Passcode required to open.
Allows locking of program and
serial flash downloads.
Passcode required to open.
Default
Description
NOT SEL
Selects source for override 2
(0)
command.
Acknowledge or disregard
(1)
permissive during override 2.
Acknowledge or disregard
(1)
interlock 1 during override 2.
Acknowledge or disregard
(1)
interlock 2 during override 2.
Acknowledge or disregard
(1)
interlock 4 during override 2.
Acknowledge or disregard
(1)
overrideable bypass faults during
override 2.
All faults can be overridden
except:
3009, 3021, 3022, 3023, 3024,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206
BYPASS
1 = Use bypass contactor only
2 = Use drive only
(1)
3 = Use drive, switch to bypass
on drive fault
4 = Both contactors open
Parameters
67