ABB ACH580 Series User Manual page 205

E-clipse bypass and packaged drive
Table of Contents

Advertisement

196
Bypass status listing
DRIVE/BYPASS?
SAFETIES?
RUN PERMISSIVES?
START REQUEST?
AUTO TRANSFER?
BYP OVERRIDE 1?
BYP OVERRIDE 2?
DRIVE FAULTED?
BYPASS FAULTED?
SYSTEM STARTED?
SYSTEM RUNNING?
BYPASS ALARMS?
HAND/OFF/AUTO?
Diagnostics
Bypass Status
(16 Characters)
DRIVE SELECTED
BYPASS SELECTED
OPEN
CLOSED
OPEN
CLOSED
NOT PRESENT
PRESENT
NOT TRANSFERRED
TRANSFERRED
NOT ACTIVATED
ACTIVATED
NOT ACTIVATED
ACTIVATED
NO
YES
NO
YES
NO
YES
NO
YES
NO ALARMS
ACTIVE
OFF MODE
HAND MODE
AUTO MODE
ACH580 E-Clipse bypass and packaged drive user manual
Condition
Displays which one is selected, drive or
bypass
Displays if safeties (=START INTERLOCK 1
and/or START INTERLOCK 2) have been
applied, or if they are missing
Displays if RUN PERMISSIVE is present or
not
Displays if start request has been applied to
the system
Displays if the system is in Auto Transfer state
or not. Does not reflect to PAR 16.08 AUTO
XFER value itself
Status of Override 1
Status of Override 2
Displays if drive is faulted or not
Displays if bypass is faulted or not
Displays if system is started or not
Displays if system is running or not
Displays if there is an active warning(s) in
bypass or not
Displays operating mode of the bypass - OFF,
HAND or AUTO
Description