ABB ACH580 Series User Manual page 204

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Warning
Warning Name In
Code
4024
Selected by PAR
1624
START
INTERLOCK 4
VIBRATION
SWITCH
...
LOW SUCTION
PRES
4025
LOCAL DISABLED
4026
AUTO DISABLED
4027
COMM CONFIG
ERR
4028
FBA PAR CONF
4029
DRIVE FAULTED
4030
OVRD2 VFD
4031
OVRD2 STOP
Warning
Panel
Warning will occur
when start order is
given and the "RUN
Permissive" is not
present
Warning is displayed if
MODE LOCK (16.29) is
set to AUTO MODE
and the Hand or Off key
is pressed
This warning is
displayed if MODE
LOCK (1629) is set to
LOCAL MODE and the
Auto key is pressed.
Warning is displayed if
the drive and bypass
MAC addresses are
equal or invalid.
Non embedded
fieldbus has detected
an error in Group 51
parameters
The drive is faulted.
Warning is generated
when override 2 is
active and the drive is
controlling the motor
Warning is generated
when override 2 is
active and both the
bypass and drive
output contactors are
deenergized
Possible Cause
Run Permissive
Check 24 Volts on
condition is not
RBCU unit
satisfied.
Check for 24 volts on
Bad 24 V supply
respective DI when
condition is satisfied
Bad digital input
Check Parameter 0103
24 V common is not
For status of digital
tied to Digital input
input
common on bypass
when using external
24 V supply
E-Clipse parameters
Change MAC address
5003 (BP MAC ID) and
to unique values
5803 (DV MAC ID) are
set to the same value
Verify Group 51
parameters
Reset drive
N/A
Check Parameter 0103
and 0104 for digital
input status
N/A
Check Parameter 0103
and 0104 for digital
input status
195
Corrective Action
Diagnostics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents