ABB ACH580 Series User Manual page 108

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Parameter
Number
5812
DV CRC
ERR
5819
DV STATUS
5813
5013
TOKEN CNT
(BACnet
Only)
5808
DV OK MSG
1) Reset by pressing UP and DOWN arrows simultaneously in edit mode. Save change by pressing
ENTER.
Display on
Panel
Possible Cause
(Symptom)
Rapidly
1. Duplicate
Increasing
Addresses
Numeric
2. Too many devices
1
Value
on wire
3. Noise on EIA-485
wire
IDLE
1. No network
connection
2. Blown EIA-485
transceiver
Not
1. Drive device
Increasing
address parameter
Numeric
5803 is set to 128 or
Value
greater.
2. E-Clipse Bypass
device address
parameter 5003 is
set to 128 or greater.
3. Max Masters is set
too low on all drives.
OK
1. Master/Client not
Message
communicating with
Counter not
drive.
1
increasing
2. Failed router
Corrective Action
1. See Corrective Action 1. Parameter
Number 5811
2. Limit to 31 unit loads on 1 segment
(Bypass = 1 unit load)
3. See Corrective Action 6. Parameter
Number 5811
1. Land communication wires as shown in
drawings on page 78. Check Repeater (if
installed onsite)
2. See Corrective Action 7. Parameter
Number 5811
3. Change application number in the
Siemens field panel.
1. Change parameter 5803 to a unique value
below 128.
2. Change parameter 5003 to a unique value
below 128.
Note: The default value for parameter
5003 is 256. This setting prevents the
network from seeing the bypass. Change
this setting ONLY if the bypass will be
seen as a node on the network.
3. Change Max Masters property at all
devices on bus to 127.
1. Add device and points to the building
control system.
2. Replace router.
Embedded fieldbus
99