ABB ACH580 Series User Manual page 120

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Number
BI16
BI17
BI18
BI19
BI20
BI21
BI22
BI23
BI24
N2 binary output objects – Bypass
The following table lists the N2 Binary Output objects defined for the ABB E-Clipse
bypass.
Number
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
BO15
BO16
BO17
BO18
BO19
Object
RELAY 1 STATUS
RELAY 2 STATUS
RELAY 3 STATUS
RELAY 4 STATUS
RELAY 5 STATUS
BYPASS MODE
SYS UNDERLOAD
SYS FAULT
BYPASS RUNNING
Object
SYSTEM START
SYS RUN PERMISSIVE
SYSTEM RESET
OVERRIDE
COMMAND RO 1
COMMAND RO 2
COMMAND RO 3
COMMAND RO 4
COMMAND RO 5
SYS INTERLOCK 1
SYS INTERLOCK 2
SYS INTERLOCK 3
SYS INTERLOCK 4
RESET KW HOURS
RESET RUN TIME
PAR LOCK
N2 LOCAL MODE
READ MB
WRITE MB
N2 Binary Inputs:
Drive Parameter
0104 (bit mask 1)
0104 (bit mask 2)
0104 (bit mask 4)
0104 (bit mask 8)
0104 (bit mask 10h)
Status Word
Status Word
Status Word
Status Word
N2 Binary Outputs:
Drive Parameter
Command Word
1 = Started
Command Word
1 = Enable
Command Word
Change 0 -> 1 Resets
Command Word
1 = Override
107 (bit mask 1)
1 = On
107 (bit mask 2)
1 = On
107 (bit mask 4)
1 = On
107 (bit mask 8)
1 = On
107 (bit mask 10h)
1 = On
Command Word
1 = Enable
Command Word
1 = Enable
Command Word
1 = Enable
Command Word
1 = Enable
0106
Bypass-mode kilowatt hours - RESET
0108
0...65535 - RESET
1619
0 = LOCKED, 1 = OPEN
Command Word
0 = AUTO, 1 = N2 LOCAL
N/A
0 = NO, 1 = READ
N/A
0 = NO, 1 = WRITE
Range
1 = On
1 = On
1 = On
1 = On
1 = On
0 = Drive mode, 1 = Bypass mode
1 = System Underload
1 = System Fault
1 = Bypass Running
Range
Embedded fieldbus
111

Hide quick links:

Advertisement

Table of Contents
loading