88
Drive Parameter
13.12 AO1 Source
13.91 AO1 Data Storage
13.22 AO2 Content Sel
13.92 AO2 Data Storage
PID control setpoint source
Using the fieldbus for the PID control setpoint requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied setpoint value in the appropriate location. (As defined
in
Drive Parameter
40.16
Set 1 setpoint 1
source
40.17
Set 1 setpoint 2
source
40.18
Set 1 setpoint
function
NOTE: For 41.16 – 41.18, PID set 2 can be used. Setpoint data storage still uses 40.92, even when PID set 2 is used.
Embedded fieldbus
Value
37, AO1 Data Storage
–
38, AO2 Data Storage
–
Analog output
control)
Value
24 (Setpoint data
storage)
3 (AI1 scaled)
0 (In1)
1 (In1+In2)
3 (In1*In2)
ACH580 E-Clipse bypass and packaged drive user manual
Setting
Analog Output 1
controlled by writing to
parameter 13.91.
Analog Output 2
controlled by writing to
parameter 13.92.
Description
Communication channel setpoint
source
Optional analog input value. Needed if
combining communication reference
with analog input value
Setpoint is 40.92 value itself/+AI1/*AI1
Protocol Reference
Modbus
N2
ABB
DCU
DRV
PROFILE
–
–
403419
AO14
–
–
403420
AO15
Protocol Reference
–
–
–
BACnet
–
AO0
–
AO1