ABB ACH580 Series User Manual page 138

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Analog value object instance summary – Drive
The following table summarizes the Analog Value Objects supported:
Instance
ID
AV0
AV1
AV2
AV3
AV4
AV5
AV6
AV7
AV8
AV9
AV10
AV11
AV12
Object Name
OUTPUT
This object indicates the calculated motor
SPEED
speed in RPM. The corresponding drive
parameter is 01.01.
OUTPUT FREQ This object indicates the output
frequency applied to the motor in Hz. The
corresponding drive parameter is 01.06.
DC BUS VOLT
This object indicates the drive's DC bus
voltage level. The corresponding drive
parameter is 01.11.
OUTPUT VOLT
This object indicates the AC output
voltage applied to the motor. The
corresponding drive parameter is 01.13.
CURRENT
This object indicates the measured
output current. The corresponding drive
parameter is 01.07.
TORQUE
This object indicates the calculated motor
output torque as a percentage of nominal
torque. The corresponding drive
parameter is 01.10.
POWER
This object indicates the measured
output power in kW. The corresponding
drive parameter is 01.14.
DRIVE TEMP
This object indicates the measured
heatsink temperature expressed as
percent where:
0% = 0°C (32°F)
100% = Fault limit
The corresponding drive parameter is
05.11
KWH (R)
This object indicates, in kW hours, the
drive's accumulated energy usage since
the last reset. The value can be reset to
zero. The corresponding drive parameter
is 01.58.
KWH (NR)
This object indicates the drive's
accumulated energy usage in MW hours.
The value cannot be reset.
PRC PID FBCK
This object is the Process PID feedback
signal. The corresponding drive
parameter is 40.97.
PRC PID DEV
This object is the Process PID output
signal's deviation from its setpoint. The
corresponding drive parameter is 40.99.
EXT PID FBCK
This object is the External PID feedback
signal. Calculated as (drive parameter
71.02) / drive parameter 71.14).
Description
129
Present Value
Units
Access Type
RPM
R
Hertz
R
Volts
R
Volts
R
Amps
R
Percent
R
Kilowatts
R
Percent
R
kWh
W
MWh
R
Percent
R
Percent
R
Percent
R
Embedded fieldbus