ACH580 E-Clipse bypass and packaged drive user manual
Only required for E-Clipse parameter selections:
1708, OVRD2 MODE [2] VFD or [3] VFD/BYPASS
The parameters in this section program the ACH580 VFDs operation during Override Mode.
Parameter
95.21
70.02
70.03
70.04
70.05
70.06
70.20
70.21
70.22
Initial Programming for Override function using OVRD2, via parameters
Parameter Name
HW option word 2
Override enable
Override activation source
Override reference source
Override direction
Override frequency
Override fault handling
Override Auto reset trials
Override Auto reset time
Parameter Value
Bit 5: Bypass present
Bit 8: Legacy bypass
present
[0] Off
[1] On
[2] On, critical
[5] DI5 high
[0] Constant speed/freq
[1] AI1
[2] AI2
[3] Override speed/freq
[4] Motor potentiometer
[5] Stop
[6] Process PID set1
[0] Forward
[1] Reverse
[2] to [7], DI1 to DI6
[8] to [13], -DI1 to -DI6
[9] Other
-500 Hz to 500 Hz
[0] Fault on high priority
[1] Autoreset
Integer value: 1 to 5
Value from
5.0 to 120.0 secs
The drive should first be set up and operating
correctly with the E-Clipse Bypass.
Comments
Verify that the Drive is set up for E-Clipse
bypass. Word value for 95.21 = [1] E-Clipse
bypass is = 0010 0000.
Default is [0] Off
Off: Override is not being used,
On: Uses programmed number of fault
resets,
On, Critical: infinite number of fault
resets.
Contacts closing against the drive's DI5 will
activate Override Mode in the ACH580 VFD.
Defaults to [3] Override speed/freq
The drive will use the Hz value programmed
in 70.06
Note that [0] Constant speed/freq is similar
Defaults to [0] Forward
Defaults to 0.0 Hz. Set the value the drive
will control to in Override when 70.04 is [3].
Defaults to [1] Fault on high priority.
Defaults to 5 times.
Defaults to 5.0 seconds.
E-Clipse bypass functions overview
39